- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Wire Stripping Length:
- 31 mm || 61 mm
- Awg Gauge:
- 2 x AWG 2/0...500 kcmil aluminium/copper
- Device Application:
- distribution
- Range:
- PowerPact
- Pollution Degree:
- 3 IEC 60947-1
- Continuous Current Rating:
- 0.8
- Protection Technology:
- current limiter
- Utilisation Category:
- category A
- Terminal Identifier:
- AL600LS52K3
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Mercury Free:
- Yes
- Rohs Exemption Information:
- Yes
- Depth:
- 110 mm
- Mounting Mode:
- unit mount lug)
- Control Type:
- toggle
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Breaking Capacity Code:
- D
- Product Name:
- PowerPact L
- Device Short Name:
- L-Frame
- Eu Rohs Directive:
- Compliant with Exemptions
- Color:
- Black
- Tightening Torque:
- 50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
- Ambient Air Temperature For Storage:
- -50-85 °C
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Circularity Profile:
- ENVEOLI2206029EN
- Trip Unit Name:
- MicroLogic 3.3
- Environmental Disclosure:
- ENVPEP2206029EN
- Sustainable Offer Status:
- Green Premium product
- Ip Degree Of Protection:
- front cover IP40
- Suitability For Isolation:
- yes IEC 60947-2
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Pvc Free:
- Yes
- Circuit Breaker Application:
- HACR rated
- Mounting Support:
- lug
- Communication Interface:
- Modbus || Ethernet
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3, LI
- Height:
- 340 mm
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Net Weight:
- 6.2 kg
- Warranty:
- 18 months
- Electrical Connection:
- lugs, line || terminal nut, load
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Network Frequency:
- 50/60 Hz
- Product Or Component Type:
- circuit breaker
- Width:
- 140 mm
- Ambient Air Temperature For Operation:
- -2-70 °C
- Product Certifications:
- UL || CSA || NOM
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Poles Description:
- 3P
- Line Rated Current:
- 400-400 A
- Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz UL 489 || 14 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489