Schneider Electric LGA34250WU33X Molded Case Circuit Breaker 480V 400A

(No reviews yet) Write a Review
SKU:
LGA34250WU33X
UPC:
3606486284131
Condition:
New
Environmental Disclosure:
ENVPEP2206029EN
Height:
340 mm
Suitability For Isolation:
yes IEC 60947-2
Rohs Exemption Information:
Yes
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Breaking Capacity Code:
G
Local Signalling:
ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
Warranty:
18 months
Electrical Connection:
I-Line connection, line || lugs, load
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Trip Unit Technology:
electronic, standard, MicroLogic 3.3 S, LSI
Device Application:
distribution
[Ue] Rated Operational Voltage:
480/277 V AC 50/60 Hz IEC 60947-3
Circuit Breaker Application:
HACR rated
Awg Gauge:
AWG 2...600 kcmil copper || AWG 2...500 kcmil aluminium
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Ambient Air Temperature For Operation:
-2-70 °C
Mounting Height:
6 in
Mercury Free:
Yes
Phase Connection:
ABC
Product Certifications:
UL || CSA || NOM
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
[Ics] Rated Service Breaking Capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Terminal Identifier:
AL400L61K3
Mounting Support:
bracket
Protection Technology:
current limiter
Sustainable Offer Status:
Green Premium product
Device Short Name:
L-Frame
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Network Frequency:
50/60 Hz
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Pvc Free:
Yes
Long Time Pick-Up Adjustment Range:
0.25...1 x In
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Net Weight:
6.2 kg
Tightening Torque:
50-50 N.m 35-300 mm² (AWG 2...600 kcmil) || 50-50 N.m 35-240 mm² (AWG 2...500 kcmil)
Breaking Capacity:
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
Trip Unit Name:
MicroLogic 3.3 S
Eu Rohs Directive:
Compliant with Exemptions
Communication Interface:
Modbus || Ethernet
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Product Name:
PowerPact L
Ambient Air Temperature For Storage:
-50-85 °C
Mounting Mode:
I-Line bracket)
Color:
Black
Poles Description:
3P
Width:
140 mm
Pollution Degree:
3 IEC 60947-1
Continuous Current Rating:
0.8
Range:
PowerPact
Wire Stripping Length:
31 mm
Circularity Profile:
ENVEOLI2206029EN
Line Rated Current:
250-250 A
Product Or Component Type:
circuit breaker
Depth:
110 mm
Control Type:
toggle
Utilisation Category:
category A
Ip Degree Of Protection:
front cover IP40
Brochure:
View
Catalog:
View
Datasheet:
View
$6,990.00

Description

PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 250A, 3 pole, circuit breaker has an interrupting rating of 35kA at 480VAC. This circuit breaker provides MicroLogic Standard with a 3.3S trip unit and an LSI function. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. This breaker is a PowerPact Mission Critical; it analyzes fault current to make decisions which maximize selectivity with downstream circuit breakers. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose