- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Pvc Free:
- Yes
- Depth:
- 110 mm
- Ambient Air Temperature For Operation:
- -2-70 °C
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Communication Interface:
- Modbus || Ethernet
- Tightening Torque:
- 50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
- Mercury Free:
- Yes
- Sustainable Offer Status:
- Green Premium product
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Mounting Mode:
- unit mount busbar)
- Environmental Disclosure:
- ENVPEP2206029EN
- Protection Technology:
- current limiter
- Suitability For Isolation:
- yes IEC 60947-2
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Electrical Connection:
- busbar connection, line || busbar connection, load
- Breaking Capacity Code:
- G
- Terminal Identifier:
- AL600LS52K3
- Product Certifications:
- UL || CSA || NOM
- Poles Description:
- 3P
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Eu Rohs Directive:
- Compliant with Exemptions
- Ambient Air Temperature For Storage:
- -50-85 °C
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3, LI
- Control Type:
- toggle
- Circuit Breaker Application:
- HACR rated
- Network Frequency:
- 50/60 Hz
- Product Or Component Type:
- circuit breaker
- Warranty:
- 18 months
- Ip Degree Of Protection:
- front cover IP40
- Width:
- 140 mm
- Color:
- Black
- Trip Unit Name:
- MicroLogic 3.3
- Circularity Profile:
- ENVEOLI2206029EN
- Line Rated Current:
- 400-400 A
- Utilisation Category:
- category A
- Mounting Support:
- busbar
- Awg Gauge:
- 2 x AWG 2/0...500 kcmil aluminium/copper
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Wire Stripping Length:
- 31 mm || 61 mm
- Device Short Name:
- L-Frame
- Net Weight:
- 6.2 kg
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Device Application:
- distribution
- Height:
- 340 mm
- Product Name:
- PowerPact L
- Range:
- PowerPact
- Rohs Exemption Information:
- Yes
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Pollution Degree:
- 3 IEC 60947-1
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Continuous Current Rating:
- 0.8