- Trip Unit Name:
- MicroLogic 3.3
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Control Type:
- toggle
- Line Rated Current:
- 600-600 A
- Ip Degree Of Protection:
- front cover IP40
- Product Certifications:
- UL || CSA || NOM
- Circularity Profile:
- ENVEOLI2206029EN
- Terminal Identifier:
- AL600LS52K3
- Device Application:
- distribution
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Wire Stripping Length:
- 31 mm || 61 mm
- Width:
- 140 mm
- Color:
- Black
- Device Short Name:
- L-Frame
- Range:
- PowerPact
- Eu Rohs Directive:
- Compliant with Exemptions
- Product Name:
- PowerPact L
- Suitability For Isolation:
- yes IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Pollution Degree:
- 3 IEC 60947-1
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3, LI
- Sustainable Offer Status:
- Green Premium product
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Network Frequency:
- 50/60 Hz
- Mounting Mode:
- unit mount busbar)
- Continuous Current Rating:
- 0.8
- Poles Description:
- 3P
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Depth:
- 110 mm
- Breaking Capacity Code:
- G
- Rohs Exemption Information:
- Yes
- Height:
- 340 mm
- Ambient Air Temperature For Storage:
- -50-85 °C
- Net Weight:
- 6.2 kg
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Product Or Component Type:
- circuit breaker
- Warranty:
- 18 months
- Communication Interface:
- Modbus || Ethernet
- Awg Gauge:
- 2 x AWG 2/0...500 kcmil aluminium/copper
- Electrical Connection:
- busbar connection, line || busbar connection, load
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Pvc Free:
- Yes
- Tightening Torque:
- 50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
- Utilisation Category:
- category A
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- Ambient Air Temperature For Operation:
- -2-70 °C
- Mercury Free:
- Yes
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Mounting Support:
- busbar
- Environmental Disclosure:
- ENVPEP2206029EN