- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3, LI
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Color:
- Black
- Circularity Profile:
- ENVEOLI2206029EN
- Awg Gauge:
- 2 x AWG 2/0...500 kcmil aluminium/copper
- Control Type:
- toggle
- Environmental Disclosure:
- ENVPEP2206029EN
- Breaking Capacity Code:
- G
- Product Certifications:
- UL || CSA || NOM
- Pvc Free:
- Yes
- Mercury Free:
- Yes
- Network Frequency:
- 50/60 Hz
- Tightening Torque:
- 50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
- Device Application:
- distribution
- Sustainable Offer Status:
- Green Premium product
- Ip Degree Of Protection:
- front cover IP40
- Rohs Exemption Information:
- Yes
- Suitability For Isolation:
- yes IEC 60947-2
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Trip Unit Name:
- MicroLogic 3.3
- Height:
- 340 mm
- Circuit Breaker Application:
- HACR rated
- Pollution Degree:
- 3 IEC 60947-1
- Communication Interface:
- Modbus || Ethernet
- Continuous Current Rating:
- 1
- Device Short Name:
- L-Frame
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Product Or Component Type:
- circuit breaker
- Ambient Air Temperature For Storage:
- -50-85 °C
- Eu Rohs Directive:
- Compliant with Exemptions
- Utilisation Category:
- category A
- Wire Stripping Length:
- 31 mm || 61 mm
- Mounting Support:
- lug
- Terminal Identifier:
- AL600LS52K3
- Mounting Mode:
- unit mount lug)
- Poles Description:
- 3P
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Line Rated Current:
- 400-400 A
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Net Weight:
- 6.2 kg
- Width:
- 140 mm
- Warranty:
- 18 months
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Depth:
- 110 mm
- Electrical Connection:
- terminal nut, line || lugs, load
- Product Name:
- PowerPact L
- Range:
- PowerPact
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Ambient Air Temperature For Operation:
- -2-70 °C
- QN-QUOTE-REQUEST:
- true