Schneider Electric LJA36250U31X Molded Case Circuit Breaker 600V 400A
Schneider Electric
$8,773.00
PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 250A, 3 pole, circuit breaker has an interrupting rating of 25kA at 600VAC. This circuit breaker provides MicroLogic Standard with a 3.3 trip unit and an LI function. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Pollution Degree:
- 3 IEC 60947-1
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Awg Gauge:
- AWG 2...600 kcmil copper || AWG 2...500 kcmil aluminium
- Tightening Torque:
- 50-50 N.m 35-300 mm² (AWG 2...600 kcmil) || 50-50 N.m 35-240 mm² (AWG 2...500 kcmil)
- Mercury Free:
- Yes
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Poles Description:
- 3P
- Terminal Identifier:
- AL400L61K3
- Wire Stripping Length:
- 31 mm
- Network Frequency:
- 50/60 Hz
- Eu Rohs Directive:
- Compliant with Exemptions
- Product Or Component Type:
- circuit breaker
- Height:
- 340 mm
- Continuous Current Rating:
- 0.8
- Mounting Mode:
- I-Line bracket)
- Line Rated Current:
- 250-250 A
- Warranty:
- 18 months
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Electrical Connection:
- I-Line connection, line || lugs, load
- Ambient Air Temperature For Storage:
- -50-85 °C
- Mounting Support:
- bracket
- Pvc Free:
- Yes
- Width:
- 140 mm
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Product Certifications:
- UL || CSA || NOM
- Range:
- PowerPact
- Sustainable Offer Status:
- Green Premium product
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Breaking Capacity Code:
- J
- Phase Connection:
- ABC
- Communication Interface:
- Modbus || Ethernet
- Utilisation Category:
- category A
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Device Application:
- distribution
- Color:
- Black
- Circularity Profile:
- ENVEOLI2206029EN
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Trip Unit Name:
- MicroLogic 3.3
- Circuit Breaker Application:
- HACR rated
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Environmental Disclosure:
- ENVPEP2206029EN
- Ambient Air Temperature For Operation:
- -2-70 °C
- Depth:
- 110 mm
- Suitability For Isolation:
- yes IEC 60947-2
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Product Name:
- PowerPact L
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Control Type:
- toggle
- Net Weight:
- 6.2 kg
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Ip Degree Of Protection:
- front cover IP40
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3, LI
- Mounting Height:
- 6 in
- Rohs Exemption Information:
- Yes
- Device Short Name:
- L-Frame