PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 600A, 3 pole, circuit breaker has an interrupting rating of 25kA at 600VAC. This circuit breaker provides MicroLogic Ammeter with a 6.3A trip unit and an LSIG function. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Poles Description:
- 3P
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Sustainable Offer Status:
- Green Premium product
- Device Short Name:
- L-Frame
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Mounting Height:
- 6 in
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Ambient Air Temperature For Storage:
- -50-85 °C
- Electrical Connection:
- I-Line connection, line || lugs, load
- Network Frequency:
- 50/60 Hz
- Warranty:
- 18 months
- Ip Degree Of Protection:
- front cover IP40
- Control Type:
- toggle
- Tightening Torque:
- 50-50 N.m 70-240 mm² (2 x AWG 2/0...500 kcmil) || 50-50 N.m 35-300 mm² (AWG 2...600 kcmil)
- Net Weight:
- 6.2 kg
- Color:
- Black
- Circuit Breaker Application:
- HACR rated
- Ambient Air Temperature For Operation:
- -2-70 °C
- Terminal Identifier:
- AL600LF52K3
- Device Application:
- distribution
- Depth:
- 110 mm
- Awg Gauge:
- 2 x AWG 2/0...500 kcmil aluminium/copper
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Height:
- 340 mm
- Environmental Disclosure:
- ENVPEP2206029EN
- Range:
- PowerPact
- Communication Interface:
- Modbus || Ethernet
- Product Or Component Type:
- circuit breaker
- Mercury Free:
- Yes
- Protection Technology:
- current limiter
- Phase Connection:
- ABC
- Trip Unit Name:
- MicroLogic 6.3 A
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Mounting Support:
- bracket
- Mounting Mode:
- I-Line bracket)
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 6.3 A, LSIG
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Wire Stripping Length:
- 31 mm
- Product Name:
- PowerPact L
- Line Rated Current:
- 600-600 A
- Breaking Capacity Code:
- J
- Rohs Exemption Information:
- Yes
- Continuous Current Rating:
- 0.8
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Pvc Free:
- Yes
- Utilisation Category:
- category A
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Pollution Degree:
- 3 IEC 60947-1
- Circularity Profile:
- ENVEOLI2206029EN
- Suitability For Isolation:
- yes IEC 60947-2
- Eu Rohs Directive:
- Compliant with Exemptions
- Product Certifications:
- UL || CSA || NOM
- Width:
- 140 mm
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View