- Awg Gauge:
- 2 x AWG 2/0...500 kcmil aluminium/copper
- Product Certifications:
- UL || CSA || NOM
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Color:
- Black
- Warranty:
- 18 months
- Protection Technology:
- current limiter
- Ambient Air Temperature For Operation:
- -2-70 °C
- Net Weight:
- 6.2 kg
- Tightening Torque:
- 50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
- Width:
- 140 mm
- Depth:
- 110 mm
- Pvc Free:
- Yes
- Electrical Connection:
- lugs, line || lugs, load
- Terminal Identifier:
- AL600LS52K3
- Device Short Name:
- L-Frame
- Ip Degree Of Protection:
- front cover IP40
- Line Rated Current:
- 400-400 A
- Rohs Exemption Information:
- Yes
- Range:
- PowerPact
- Suitability For Isolation:
- yes IEC 60947-2
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Network Frequency:
- 50/60 Hz
- Communication Interface:
- Modbus || Ethernet
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Utilisation Category:
- category A
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Device Application:
- distribution
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Eu Rohs Directive:
- Compliant with Exemptions
- Environmental Disclosure:
- ENVPEP2206029EN
- Trip Unit Name:
- MicroLogic 3.3
- Wire Stripping Length:
- 31 mm || 61 mm
- Circularity Profile:
- ENVEOLI2206029EN
- Breaking Capacity Code:
- J
- Sustainable Offer Status:
- Green Premium product
- Mercury Free:
- Yes
- Mounting Mode:
- unit mount lug)
- Product Or Component Type:
- circuit breaker
- Continuous Current Rating:
- 0.8
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Pollution Degree:
- 3 IEC 60947-1
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3, LI
- Ambient Air Temperature For Storage:
- -50-85 °C
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Control Type:
- toggle
- Mounting Support:
- lug
- Height:
- 340 mm
- Poles Description:
- 3P
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Circuit Breaker Application:
- HACR rated
- Product Name:
- PowerPact L