Schneider Electric LJL36600U33X Molded Case Circuit Breaker 480V 400A
Schneider Electric
$11,134.00
$1200 Minimum Order for Non-stock Items or $60 Addl Schneider Handling Fee Applies
PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 600A, 3 pole, circuit breaker has an interrupting rating of 25kA at 600VAC. This circuit breaker provides MicroLogic Standard with a 3.3S trip unit and an LSI function. This unit has lugs on both the line and load sides. This circuit breaker has a continuous current rating of 80%. This circuit breaker has a continuous current rating of 80%. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Continuous Current Rating:
- 0.8
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Poles Description:
- 3P
- Device Application:
- distribution
- Wire Stripping Length:
- 31 mm || 61 mm
- Pollution Degree:
- 3 IEC 60947-1
- Product Or Component Type:
- circuit breaker
- Awg Gauge:
- 2 x AWG 2/0...500 kcmil aluminium/copper
- Ambient Air Temperature For Storage:
- -50-85 °C
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Circuit Breaker Application:
- HACR rated
- Height:
- 340 mm
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Network Frequency:
- 50/60 Hz
- Breaking Capacity Code:
- J
- Mounting Mode:
- unit mount lug)
- Tightening Torque:
- 50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
- Environmental Disclosure:
- ENVPEP2206029EN
- Rohs Exemption Information:
- Yes
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Range:
- PowerPact
- Circularity Profile:
- ENVEOLI2206029EN
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Color:
- Black
- Mounting Support:
- lug
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Sustainable Offer Status:
- Green Premium product
- Ip Degree Of Protection:
- front cover IP40
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3 S, LSI
- Communication Interface:
- Modbus || Ethernet
- Width:
- 140 mm
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Mercury Free:
- Yes
- Ambient Air Temperature For Operation:
- -2-70 °C
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Trip Unit Name:
- MicroLogic 3.3 S
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Utilisation Category:
- category A
- Eu Rohs Directive:
- Compliant with Exemptions
- Depth:
- 110 mm
- Terminal Identifier:
- AL600LS52K3
- Product Certifications:
- UL || CSA || NOM
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Product Name:
- PowerPact L
- Device Short Name:
- L-Frame
- Control Type:
- toggle
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Line Rated Current:
- 600-600 A
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Pvc Free:
- Yes
- Net Weight:
- 6.2 kg
- Electrical Connection:
- lugs, line || lugs, load
- Warranty:
- 18 months
- Suitability For Isolation:
- yes IEC 60947-2
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View