- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Suitability For Isolation:
- yes IEC 60947-2
- Continuous Current Rating:
- 0.8
- Product Certifications:
- UL || CSA || NOM
- Protection Technology:
- current limiter
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Trip Unit Name:
- MicroLogic 3.3 S
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Mercury Free:
- Yes
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Electrical Connection:
- lugs, line || terminal nut, load
- Color:
- Black
- Circularity Profile:
- ENVEOLI1406010EN
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Control Type:
- toggle
- Depth:
- 110 mm
- Awg Gauge:
- 2 x AWG 2/0...500 kcmil aluminium/copper
- Pollution Degree:
- 3 IEC 60947-1
- Sustainable Offer Status:
- Green Premium product
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Eu Rohs Directive:
- Compliant
- Breaking Capacity Code:
- J
- Device Short Name:
- L-Frame
- Pvc Free:
- Yes
- Wire Stripping Length:
- 31 mm || 61 mm
- Mounting Mode:
- unit mount lug)
- Warranty:
- 18 months
- Net Weight:
- 6.2 kg
- Communication Interface:
- Modbus || Ethernet
- Line Rated Current:
- 400-400 A
- Mounting Support:
- lug
- Device Application:
- distribution
- Product Or Component Type:
- circuit breaker
- Range:
- PowerPact
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Height:
- 340 mm
- Width:
- 140 mm
- Ambient Air Temperature For Operation:
- -2-70 °C
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Network Frequency:
- 50/60 Hz
- Environmental Disclosure:
- ENVPEP1406010EN
- Utilisation Category:
- category A
- Ambient Air Temperature For Storage:
- -50-85 °C
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Terminal Identifier:
- AL600LS52K3
- Poles Description:
- 3P
- Product Name:
- PowerPact L
- Circuit Breaker Application:
- HACR rated
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3 S, LSI
- Ip Degree Of Protection:
- front cover IP40
- Rohs Exemption Information:
- Yes
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Tightening Torque:
- 50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)