- Terminal Identifier:
- AL600LS52K3
- Wire Stripping Length:
- 31 mm || 61 mm
- Product Name:
- PowerPact L
- Device Short Name:
- L-Frame
- Continuous Current Rating:
- 0.8
- Accessory / Separate Part Type:
- shunt trip cover frame
- Mounting Mode:
- unit mount lug)
- Network Frequency:
- 50/60 Hz
- Width:
- 140 mm
- Color:
- Black
- Pollution Degree:
- 3 IEC 60947-1
- Protection Technology:
- current limiter
- Trip Unit Name:
- MicroLogic 3.3
- Mounting Support:
- lug
- Ip Degree Of Protection:
- front cover IP40
- Breaking Capacity Code:
- J
- Rohs Exemption Information:
- Yes
- Environmental Disclosure:
- ENVPEP2206029EN
- Mercury Free:
- Yes
- Device Application:
- distribution
- Breaking Capacity:
- 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489
- Height:
- 340 mm
- Product Certifications:
- UL || CSA || NOM
- Product Or Component Type:
- circuit breaker
- Circularity Profile:
- ENVEOLI2206029EN
- Awg Gauge:
- 2 x AWG 2/0...500 kcmil aluminium/copper
- Range:
- PowerPact
- Pvc Free:
- Yes
- Depth:
- 110 mm
- Ambient Air Temperature For Operation:
- -2-70 °C
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Tightening Torque:
- 50-50 N.m 70-240 mm² (AWG 2/0...500 kcmil)
- Line Rated Current:
- 600-600 A
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- Electrical Connection:
- terminal nut, line || lugs, load
- Suitability For Isolation:
- yes IEC 60947-2
- Warranty:
- 18 months
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Utilisation Category:
- category A
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Sustainable Offer Status:
- Green Premium product
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Control Type:
- toggle
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Communication Interface:
- Modbus || Ethernet
- Circuit Breaker Application:
- HACR rated
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Eu Rohs Directive:
- Compliant with Exemptions
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3, LI
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Poles Description:
- 3P
- Ambient Air Temperature For Storage:
- -50-85 °C
- Net Weight:
- 6.2 kg
- QN-QUOTE-REQUEST:
- true