Schneider Electric

Schneider Electric LU2B12BL Reverser 12A 24Vdc

(No reviews yet) Write a Review
SKU:
LU2B12BL
UPC:
3389110362930
Condition:
New
Warranty:
18 months
[Ue] Rated Operational Voltage:
690 V AC power circuit
Typical Current Consumption:
120 mA 24 V DC I maximum while closing || 120 mA 24 V DC I rms sealed
Device Application:
motor control || motor protection
[Ie] Rated Operational Current:
12 A <= 440 V || 12 A 500 V || 9 A 690 V
[Uc] Control Circuit Voltage:
24 V DC
Net Weight:
1.27 kg
Rohs Exemption Information:
Yes
Product Or Component Type:
reversing power base
Fixing Mode:
clipped DIN rail) || screw-fixed plate)
Depth:
126 mm
Height:
224 mm
Vibration Resistance:
2 gn 5-300 Hz) power poles open IEC 60068-2-27 || 4 gn 5-300 Hz) power poles closed IEC 60068-2-27
Compatibility Code:
LU2B
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mercury Free:
Yes
Resistance To Radiated Fields:
10 V/m 3 IEC 61000-4-3
Control Circuit Voltage Limits:
14.5 V DC drop-out || 20...27 V DC in operation
Immunity To Voltage Dips:
70 % / 500 ms IEC 61000-4-11
Standards:
EN 60947-6-2 || IEC 60947-6-2 || UL 60947-4-1, with phase barrier || CSA C22.2 No 60947-4-1, with phase barrier
Protective Treatment:
TH IEC 60068
Fire Resistance:
960 °C parts supporting live components IEC 60695-2-12 || 650 °C IEC 60695-2-12
Heat Dissipation:
2-2 W control circuit with LUCA, LUCB, LUCC, LUCD || 1.7-1.7 W control circuit with LUCM
Width:
45 mm
Auxiliary Contact Composition:
1 NO + 1 NC
Operating Time:
150 ms with change of direction power circuit || 75 ms without change of direction power circuit || 35 ms opening with LUCA, LUCB, LUCC, LUCD, LUCM control circuit || 75 ms closing with LUCM control circuit || 70 ms closing with LUCA, LUCB, LUCC, LUC
Resistance To Electrostatic Discharge:
8 kV 3 in open air IEC 61000-4-2 || 8 kV 4 on contact IEC 61000-4-2
Product Name:
TeSys Ultra
[Ith] Conventional Free Air Thermal Current:
0
Product Certifications:
CE || UL || CSA || CCC || EAC || ASEFA || ATEX || Marine
Network Frequency:
40...60 Hz
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Operating Altitude:
6561.68 ft (2000 m)
Range:
TeSys
Inrush Restraint Duration:
15 ms DC
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Immunity To Radioelectric Fields:
10 V IEC 61000-4-6
Immunity To Microbreaks:
3 ms control circuit
Resistance To Fast Transients:
2 kV 3 serial link IEC 61000-4-4 || 4 kV 4 all circuits except for serial link IEC 61000-4-4
Ambient Air Temperature For Operation:
-25-60 °C with LUCM || -25-70 °C with LUCA, LUCB, LUCC, LUCD
Ambient Air Temperature For Storage:
-40-85 °C
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
California Proposition 65:
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Shock Resistance:
10 gn power poles open IEC 60068-2-27 || 15 gn power poles closed IEC 60068-2-27
Ip Degree Of Protection:
IP20 IEC 60947-1 front panel and wired terminals) || IP20 IEC 60947-1 other faces) || IP40 IEC 60947-1 front panel outside connection zone)
Poles Description:
3P
Tightening Torque:
control circuit 0.8-1.2 N.m flat 5 mm || control circuit 0.8-1.2 N.m Philips no 1 5 mm || power circuit 1.9-2.5 N.m flat 6 mm || power circuit 1.9-2.5 N.m Philips No 2 6 mm || power circuit 1.9-2.5 N.m pozidriv No 2 6 mm
[Ics] Rated Service Breaking Capacity:
50 kA 230 V || 50 kA 440 V || 10 kA 500 V || 4 kA 690 V
Mechanical Durability:
15 Mcycles
Suitability For Isolation:
yes
Eu Rohs Directive:
Compliant with Exemptions
[Ui] Rated Insulation Voltage:
690 V IEC 60947-6-2 3) || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1
Auxiliary Contacts Type:
linked contacts 1 NO + 1 NC) IEC 60947-4-1 || mirror contact 1 NC) IEC 60947-1
Utilisation Category:
AC-43 || AC-44 || AC-41
Device Short Name:
LU2B
Maximum Operating Rate:
3600 cyc/h
Product Compatibility:
control unit LUC.X6BL || control unit LUC.1XBL || control unit LUC.05BL || control unit LUC.12BL
[Uimp] Rated Impulse Withstand Voltage:
6 kVIEC 60947-6-2
Connections - Terminals:
control circuit screw clamp terminals 1 0.34-1.5 mm² flexible with cable end || control circuit screw clamp terminals 1 0.75-1.5 mm² flexible without cable end || control circuit screw clamp terminals 1 0.75-1.5 mm² rigid || control circuit screw
Safe Separation Of Circuit:
400 V SELV between the control and auxiliary circuits IEC 60947-1 appendix N || 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1 appendix N
Datasheet:
View
$488.00

Description

TeSys U standard reversing power base, 3 poles (3NO), rated 12A/690V, to be completed with a control unit LUC to form a TeSys U reversing starter controller, for 3-phase motor applications up to 5.5kW@400V. Base composed of power contacts, control coil, rotary handle, with a modular design for additional modules to form a "all in one" reversing starter controller with basic or advanced protection and control functions. It is equipped with a reverser module LU2MB0BL to be supplied with 24V DC, auxiliary signaling contacts (1NO+1NC), a control terminal block, blanking shutters covering the empty cavities. It provides a high breaking capacity Icu 50kA@400V, start-stop control guaranteed for 3600 cycles/hour. Very compact (45mm width), DIN-rail mounting and screw fixing, with a padlockable rotary handle. Certified when used in conjunction with a LUC control unit (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
View AllClose