Shock Resistance:
10 gn power poles open IEC 60068-2-27 || 15 gn power poles closed IEC 60068-2-27
Operating Altitude:
6561.68 ft (2000 m)
Maximum Operating Rate:
3600 cyc/h
Connections - Terminals:
control circuit screw clamp terminals 1 0.34-1.5 mm² flexible with cable end || control circuit screw clamp terminals 1 0.75-1.5 mm² flexible without cable end || control circuit screw clamp terminals 1 0.75-1.5 mm² rigid || control circuit screw cla
Inrush Restraint Duration:
25 ms AC 50/60 Hz || 15 ms DC
Operating Time:
150 ms with change of direction power circuit || 35 ms opening control circuit || 75 ms without change of direction power circuit || 60 ms closing control circuit
[Uc] Control Circuit Voltage:
48...72 V AC 50/60 Hz || 48...72 V DC
Resistance To Fast Transients:
2 kV 3 serial link IEC 61000-4-4 || 4 kV 4 all circuits except for serial link IEC 61000-4-4
[Ie] Rated Operational Current:
12 A <= 440 V || 12 A 500 V || 9 A 690 V
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Ambient Air Temperature For Operation:
-25-60 °C with LUCM || -25-70 °C with LUCA, LUCB, LUCC, LUCD
Depth:
126 mm
Resistance To Electrostatic Discharge:
8 kV 3 in open air IEC 61000-4-2 || 8 kV 4 on contact IEC 61000-4-2
Eu Rohs Directive:
Compliant with Exemptions
Safe Separation Of Circuit:
400 V SELV between the control and auxiliary circuits IEC 60947-1 appendix N || 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1 appendix N
Utilisation Category:
AC-43 || AC-44 || AC-41
Compatibility Code:
LU2B
Width:
45 mm
Product Name:
TeSys Ultra
[Ics] Rated Service Breaking Capacity:
50 kA 230 V || 50 kA 440 V || 10 kA 500 V || 4 kA 690 V
Mechanical Durability:
15 Mcycles
[Ui] Rated Insulation Voltage:
690 V IEC 60947-6-2 3) || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1
Product Or Component Type:
reversing power base
Warranty:
18 months
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Auxiliary Contacts Type:
linked contacts 1 NO + 1 NC) IEC 60947-4-1 || mirror contact 1 NC) IEC 60947-1
Device Short Name:
LU2B
Rohs Exemption Information:
Yes
Fire Resistance:
960 °C parts supporting live components IEC 60695-2-12 || 650 °C IEC 60695-2-12
Product Certifications:
CE || UL || CSA || CCC || EAC || ASEFA || ATEX || Marine
Typical Current Consumption:
2300 mA 48...72 V DC I maximum while closing || 2300 mA 48...72 V AC I maximum while closing
Network Frequency:
40...60 Hz
Control Circuit Voltage Limits:
29 V AC drop-out || 29 V DC drop-out || 38.5...72 V AC in operation || 38.5...93 V DC in operation
Net Weight:
1.27 kg
Heat Dissipation:
3-3 W control circuit with LUCA, LUCB, LUCC, LUCD || 1.8-1.8 W control circuit with LUCM
Ip Degree Of Protection:
IP20 IEC 60947-1 front panel and wired terminals) || IP20 IEC 60947-1 other faces) || IP40 IEC 60947-1 front panel outside connection zone)
Vibration Resistance:
2 gn 5-300 Hz) power poles open IEC 60068-2-27 || 4 gn 5-300 Hz) power poles closed IEC 60068-2-27
Fixing Mode:
clipped DIN rail) || screw-fixed plate)
Non-Dissipating Shock Wave:
1 kV serial mode IEC 60947-6-2 || 2 kV common mode IEC 60947-6-2
[Ith] Conventional Free Air Thermal Current:
0
California Proposition 65:
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Tightening Torque:
control circuit 0.8-1.2 N.m flat 5 mm || control circuit 0.8-1.2 N.m Philips no 1 5 mm || power circuit 1.9-2.5 N.m flat 6 mm || power circuit 1.9-2.5 N.m Philips No 2 6 mm || power circuit 1.9-2.5 N.m pozidriv No 2 6 mm
Poles Description:
3P
Suitability For Isolation:
yes
Immunity To Microbreaks:
3 ms control circuit
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Immunity To Voltage Dips:
70 % / 500 ms IEC 61000-4-11
Immunity To Radioelectric Fields:
10 V IEC 61000-4-6
Protective Treatment:
TH IEC 60068
Standards:
EN 60947-6-2 || IEC 60947-6-2 || UL 60947-4-1, with phase barrier || CSA C22.2 No 60947-4-1, with phase barrier
Range:
TeSys
[Uimp] Rated Impulse Withstand Voltage:
6 kVIEC 60947-6-2
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Mercury Free:
Yes
Ambient Air Temperature For Storage:
-40-85 °C
Device Application:
motor control || motor protection
Resistance To Radiated Fields:
10 V/m 3 IEC 61000-4-3
Product Compatibility:
control unit LUC.X6ES || control unit LUC.1XES || control unit LUC.05ES || control unit LUC.12ES
Auxiliary Contact Composition:
1 NO + 1 NC
Height:
224 mm
[Ue] Rated Operational Voltage:
690 V AC power circuit
$488.00

Description

TeSys U standard reversing power base, 3 poles (3NO), rated 12A/690V, to be completed with a control unit LUC to form a TeSys U reversing starter controller, for 3-phase motor applications up to 5.5kW@400V. Base composed of power contacts, control coil, rotary handle, with a modular design for additional modules to form a "all in one" reversing starter controller with basic or advanced protection and control functions. It is equipped with a reverser module LU2MB0ES to be supplied with 48V AC / 48-72V DC, auxiliary signaling contacts (1NO+1NC), a control terminal block, blanking shutters covering the empty cavities. It provides a high breaking capacity Icu 50kA@400V, start-stop control guaranteed for 3600 cycles/hour. Very compact (45mm width), DIN-rail mounting and screw fixing, with a padlockable rotary handle. Certified when used in conjunction with a LUC control unit (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).