Schneider Electric

Schneider Electric LU2MB0B Reverser Block 32A 24V Ac

(No reviews yet) Write a Review
SKU:
LU2MB0B
UPC:
3.38911E+12
Condition:
New
Depth:
105 mm
Fixing Mode:
plug-in
Fire Resistance:
960 °C parts supporting live components IEC 60695-2-12 || 650 °C IEC 60695-2-12
Mercury Free:
Yes
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Standards:
EN 60947-6-2 || IEC 60947-6-2 || UL 60947-4-1, with phase barrier || CSA C22.2 No 60947-4-1, with phase barrier
Range:
TeSys
Tightening Torque:
control circuit 0.8-1.2 N.m flat 5 mm || control circuit 0.8-1.2 N.m Philips No 2 5 mm || power circuit 1.9-2.5 N.m flat 6 mm || power circuit 1.9-2.5 N.m Philips No 2 6 mm
Width:
45 mm
Device Mounting:
direct mounting
Operating Altitude:
6561.68 ft (2000 m)
Network Frequency:
40...60 Hz
Connections - Terminals:
control circuit screw clamp terminals 1 0.34-1.5 mm² 3 mm) flexible with cable end || control circuit screw clamp terminals 1 0.75-1.5 mm² 3 mm) flexible without cable end || control circuit screw clamp terminals 1 0.75-1.5 mm² 3 mm) rigid || cont
Height:
80 mm
Ambient Air Temperature For Storage:
-40-85 °C
Resistance To Electrostatic Discharge:
8 kV level 3, in open air IEC 61000-4-2 || 8 kV level 4, on contact IEC 61000-4-2
California Proposition 65:
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Operating Time:
150 ms with change of direction || 75 ms without change of direction
Rohs Exemption Information:
Yes
Ip Degree Of Protection:
IP20 IEC 60947-1 front panel and wired terminals) || IP20 IEC 60947-1 other faces) || IP40 IEC 60947-1 front panel outside connection zone)
Protective Treatment:
TH IEC 60068
Eu Rohs Directive:
Compliant with Exemptions
[Ie] Rated Operational Current:
32 A
Vibration Resistance:
2 gn 5-300 Hz) power poles open IEC 60068-2-27 || 4 gn 5-300 Hz) power poles closed IEC 60068-2-27
Shock Resistance:
10 gn power poles open IEC 60068-2-27 || 15 gn power poles closed IEC 60068-2-27
Resistance To Radiated Fields:
10 V/m level 3 IEC 61000-4-3
[Ue] Rated Operational Voltage:
690 V AC power circuit
[Ui] Rated Insulation Voltage:
690 V IEC 60947-6-2 || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Net Weight:
0.4 kg
Current Consumption:
2360 mA 24 V AC I maximum while closing
Product Or Component Type:
reverser block
Device Application:
motor control
Inrush Restraint Duration:
25 ms AC || 15 ms DC
Product Certifications:
CE || UL || CSA || CCC || EAC || ASEFA || ATEX || Marine
Warranty:
18 months
Compatibility Code:
LU2MB
Non-Dissipating Shock Wave:
1 kV serial mode IEC 60947-6-2 || 2 kV common mode IEC 60947-6-2
[Uimp] Rated Impulse Withstand Voltage:
6 kVIEC 60947-6-2
Device Short Name:
LU2MB
Ambient Air Temperature For Operation:
-25-60 °C with LUCM || -25-70 °C with LUCA, LUCB, LUCC, LUCD
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Resistance To Fast Transients:
2 kV 3 serial link IEC 61000-4-4 || 4 kV 4 all circuits except for serial link IEC 61000-4-4
[Uc] Control Circuit Voltage:
24 V AC 50/60 Hz
Immunity To Radioelectric Fields:
10 V IEC 61000-4-6
Datasheet:
View
$192.00

Description

TeSys U reversing module for vertical mounting, for the constitution of TeSys U reversing starter controllers. It provides reverse power contacts, coil control with interlocking capabilities to be supplied with 24V AC. To be used with an advanced power base LUB120 or LUB320 equipped with a Control Unit LUC*B type. To be associated with an assembling connector LU9MR1C and a control terminal block LU9M1 to complete the vertical mounting. Green Premium compliant (RoHS/REACh).
View AllClose