Schneider Electric LUB120 Screw Clamp Base 12A

(No reviews yet) Write a Review
SKU:
LUB120
UPC:
3389110362794
Condition:
New
Width:
45 mm
[Ue] Rated Operational Voltage:
690 V AC power circuit
Utilisation Category:
AC-43 || AC-44 || AC-41
Rohs Exemption Information:
Yes
[Uc] Control Circuit Voltage:
24 V AC 50/60 Hz || 24 V DC || 48...72 V AC 50/60 Hz || 48...72 V DC || 110...240 V AC 50/60 Hz || 110...220 V DC
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Net Weight:
0.865 kg
Immunity To Voltage Dips:
70 % / 500 ms IEC 61000-4-11
Sustainable Offer Status:
Green Premium product
[Ith] Conventional Free Air Thermal Current:
0
Depth:
126 mm
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Suitability For Isolation:
yes
Mechanical Durability:
15 Mcycles
Pvc Free:
Yes
Safe Separation Of Circuit:
400 V SELV between the control and auxiliary circuits IEC 60947-1 appendix N || 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1 appendix N
Typical Current Consumption:
130 mA 24 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD || 140 mA 24 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD || 150 mA 24 V DC I maximum while closing with LUCM || 280 mA 110...220 V DC I maximum while closing with LUCA, L
Fire Resistance:
960 °C parts supporting live components IEC 60695-2-12 || 650 °C IEC 60695-2-12
Ip Degree Of Protection:
IP20 IEC 60947-1 front panel and wired terminals) || IP20 IEC 60947-1 other faces) || IP40 IEC 60947-1 front panel outside connection zone)
Protective Treatment:
TH IEC 60068
Tightening Torque:
control circuit 0.8-1.2 N.m flat 5 mm || control circuit 0.8-1.2 N.m Philips no 1 5 mm || power circuit 1.9-2.5 N.m flat 6 mm || power circuit 1.9-2.5 N.m Philips No 2 6 mm || power circuit 1.9-2.5 N.m pozidriv No 2 6 mm
Height:
154 mm
Immunity To Radioelectric Fields:
10 V IEC 61000-4-6
Standards:
EN 60947-6-2 || IEC 60947-6-2 || UL 60947-4-1, with phase barrier || CSA C22.2 No 60947-4-1, with phase barrier
Product Or Component Type:
non reversing power base
Ambient Air Temperature For Storage:
-40-85 °C
Vibration Resistance:
2 gn 5-300 Hz) power poles open IEC 60068-2-27 || 4 gn 5-300 Hz) power poles closed IEC 60068-2-27
Maximum Operating Rate:
3600 cyc/h
Product Name:
TeSys Ultra
Non-Dissipating Shock Wave:
1 kV serial mode 24...240 V AC IEC 60947-6-2 || 1 kV serial mode 48...220 V DC IEC 60947-6-2 || 2 kV common mode 24...240 V AC IEC 60947-6-2 || 2 kV common mode 48...220 V DC IEC 60947-6-2
Operating Time:
35 ms opening with LUCA, LUCB, LUCC, LUCD, LUCM control circuit || 50 ms >= 72 V closing with LUCA, LUCB, LUCC, LUCD control circuit || 60 ms 48 V closing with LUCA, LUCB, LUCC, LUCD control circuit || 70 ms 24 V closing with LUCA, LUCB, LUCC, LUCD c
Resistance To Electrostatic Discharge:
8 kV 3 in open air IEC 61000-4-2 || 8 kV 4 on contact IEC 61000-4-2
Ambient Air Temperature For Operation:
-25-60 °C with LUCM || -25-70 °C with LUCA, LUCB, LUCC, LUCD
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Poles Description:
3P
[Ie] Rated Operational Current:
12 A <= 440 V || 12 A 500 V || 9 A 690 V
Warranty:
18 months
Device Short Name:
LUB
Fixing Mode:
clipped DIN rail) || screw-fixed plate)
Circularity Profile:
ENVEOLI0802003_V1
Auxiliary Contact Composition:
1 NO + 1 NC
[Uimp] Rated Impulse Withstand Voltage:
6 kVIEC 60947-6-2
Product Certifications:
CE || UL || CSA || CCC || EAC || ASEFA || ATEX || Marine
[Ics] Rated Service Breaking Capacity:
50 kA 230 V || 50 kA 440 V || 10 kA 500 V || 4 kA 690 V
Heat Dissipation:
2-2 W control circuit with LUCA, LUCB, LUCC, LUCD || 1.7-1.7 W control circuit with LUCM
Operating Altitude:
6561.68 ft (2000 m)
Connections - Terminals:
power circuit screw clamp terminals 1 1-10 mm² rigid || power circuit screw clamp terminals 1 1-6 mm² flexible with cable end || power circuit screw clamp terminals 1 2.5-10 mm² flexible without cable end || power circuit screw clamp terminals 2 1-6
Shock Resistance:
10 gn power poles open IEC 60068-2-27 || 15 gn power poles closed IEC 60068-2-27
Range:
TeSys
Resistance To Radiated Fields:
10 V/m 3 IEC 61000-4-3
[Ui] Rated Insulation Voltage:
690 V IEC 60947-6-2 3) || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1
Network Frequency:
40...60 Hz
Environmental Disclosure:
ENVPEP080203EN_V1
Resistance To Fast Transients:
2 kV 3 serial link IEC 61000-4-4 || 4 kV 4 all circuits except for serial link IEC 61000-4-4
Mercury Free:
Yes
Device Application:
motor control || motor protection
Immunity To Microbreaks:
3 ms control circuit
Compatibility Code:
LUB
Eu Rohs Directive:
Compliant with Exemptions
Auxiliary Contacts Type:
linked contacts 1 NO + 1 NC) IEC 60947-4-1 || mirror contact 1 NC) IEC 60947-1
$275.00

Description

TeSys U advanced power base, 3 poles (3NO), 12A/690V, to be completed with a control unit LUC to form a TeSys U starter controller, for 3-phase motor applications up to 5.5kW@400V. Base composed of power contacts, control coil, rotary handle, with a modular design for additional modules to form a "all in one" starter controller with basic or advanced protection and control functions. It is equipped with auxiliary signaling contacts (1NO+1NC), a control terminal block, and blanking shutters covering the empty cavities. It provides a high breaking capacity Icu 50kA@400V, start-stop control guaranteed for 3600 cycles/hour. Very compact (45mm width), DIN-rail mounting and screw fixing, with a padlockable rotary handle. Certified when used in conjunction with a LUC control unit (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).