Schneider Electric LUCD12ES Adv Control 3-12A 48-72V

(No reviews yet) Write a Review
SKU:
LUCD12ES
UPC:
3.38911E+12
Condition:
New
Resistance To Fast Transients:
2 kV 3 serial link IEC 61000-4-4 || 4 kV 4 all circuits except for serial link IEC 61000-4-4
Product Specific Application:
basic protection and advanced functions, communication
Compatibility Code:
LUCD
Tripping Threshold:
14.2 x Ir +/- 20 %
Resistance To Radiated Fields:
10 V/m 3 IEC 61000-4-3
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Immunity To Radioelectric Fields:
10 V IEC 61000-4-6
Control Circuit Voltage Limits:
38.5...72 V AC 48 V in operation || 38.5...93 V DC 48...72 V in operation || 29 V AC 48 V drop-out || 29 V DC 48...72 V drop-out
Safe Separation Of Circuit:
400 V SELV between the control and auxiliary circuits IEC 60947-1 || 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1
Device Short Name:
LUCD
Product Certifications:
CE || UL || CSA || CCC || EAC || ASEFA || ATEX || Marine
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Heat Dissipation:
2-2 W control circuit with LUB12 || 3-3 W control circuit with LUB32 || 3-3 W control circuit with LUB38
Motor Power Kw:
5.5 kW 400...440 V AC 50/60 Hz || 5.5 kW 500 V AC 50/60 Hz || 9 kW 690 V AC 50/60 Hz
Ambient Air Temperature For Operation:
-25-70 °C
Device Application:
motor control || motor protection
Thermal Protection Adjustment Range:
3-12 A
Height:
66 mm
Ip Degree Of Protection:
IP20 front panel and wired terminals IEC 60947-1 || IP20 other faces IEC 60947-1 || IP40 front panel outside connection zone IEC 60947-1
Non-Dissipating Shock Wave:
1 kV serial mode IEC 60947-6-2 || 2 kV common mode IEC 60947-6-2
Eu Rohs Directive:
Compliant with Exemptions
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947-6-2
Operating Altitude:
6561.68 ft (2000 m)
Function Available:
earth fault protection || protection against phase failure and phase imbalance || manual reset || protection against overload and short-circuit
[Uc] Control Circuit Voltage:
48 V AC || 48...72 V DC
Utilisation Category:
AC-44 || AC-43 || AC-41
Operating Time:
35 ms opening with LUB12 control circuit || 35 ms opening with LUB32 control circuit || 35 ms opening with LUB38 control circuit || 60 ms closing with LUB12 control circuit || 60 ms closing with LUB32 control circuit || 60 ms closing with LUB38 contr
Product Or Component Type:
advanced control unit
Sustainable Offer Status:
Green Premium product
Thermal Overload Class:
class 20 40-60 Hz -25-70 °C IEC 60947-6-2 || class 20 40-60 Hz -25-70 °C UL 508
Load Type:
3-phase motor self-cooled
Circularity Profile:
ENVEOLI100414
Product Compatibility:
power base LUB12 || power base LUB32 || power base LUB38 || power base LUB120 || power base LUB320 || power base LUB380 || reversing contactor breaker LU2B12ES || reversing contactor breaker LU2B32ES
Rohs Exemption Information:
Yes
Protective Treatment:
TH IEC 60068
Reset:
manual reset
Vibration Resistance:
2 gn 5-300 Hz power poles open IEC 60068-2-6 || 4 gn 5-300 Hz power poles closed IEC 60068-2-6
Resistance To Electrostatic Discharge:
8 kV 3 in open air IEC 61000-4-2 || 8 kV 4 on contact IEC 61000-4-2
Standards:
EN 60947-6-2 || IEC 60947-6-2 || UL 60947-4-1, with phase barrier || CSA C22.2 No 60947-4-1, with phase barrier
Ambient Air Temperature For Storage:
-40-85 °C
Range:
TeSys
Halogen Content Performance:
Halogen free plastic parts product
Environmental Disclosure:
ENVPEP080204EN
Pvc Free:
Yes
Phase Failure Sensitivity:
yes
Immunity To Voltage Dips:
70 % / 500 ms IEC 61000-4-11
[Ui] Rated Insulation Voltage:
690 V IEC 60947-6-2 || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1
Mercury Free:
Yes
Product Name:
TeSys Ultra
Depth:
60 mm
Width:
45 mm
Warranty:
18 months
Fixing Mode:
plug-in front face)
[Ue] Rated Operational Voltage:
690 V AC
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Network Frequency:
40...60 Hz
Typical Current Consumption:
280 mA 48 V AC I maximum while closing with LUB12 || 280 mA 48 V AC I maximum while closing with LUB32 || 280 mA 48 V AC I maximum while closing with LUB38 || 280 mA 48...72 V DC I maximum while closing with LUB12 || 280 mA 48...72 V DC I maximum whi
Immunity To Microbreaks:
3 ms
Fire Resistance:
960 °C parts supporting live components IEC 60695-2-12 || 650 °C IEC 60695-2-12
Range Of Product:
TeSys Ultra
Shock Resistance:
10 gn power poles open IEC 60068-2-27 || 15 gn power poles closed IEC 60068-2-27
Catalog:
View
Datasheet:
View
  • Schneider Electric LUCD12ES Adv Control 3-12A 48-72V
  • Schneider Electric LUCD12ES Adv Control 3-12A 48-72V
$150.00

Description

TeSys U control and diagnostic unit to be inserted in advanced power bases LUB120, LUB320, LUB380 to form a TeSys U starter controller, for 3-phase motor applications up to 5.5kW@400V. It provides full protection to motors with a rated current Ir 3-12A (Ir adjustable), overload tripping class 20, short circuit at 13 x Irmax, overcurrent at 14.2 x Ir, phase loss, insulation fault (protection of equipment only). For diagnostics, it provides a thermal overload alarm to be managed with an additional function module (to be ordered separately) and a test push button for overload simulation. To be used with a 48V AC / 48-72V DC voltage for the control of the starter (through the control terminals A1/A2 located in the power base). Certified when used in conjunction with a LUB power base (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
View AllClose