Schneider Electric LV426842 Coil Mx Ac 48 V 50/60 Hz
Schneider Electric
$930.00
$1200 Minimum Order for Non-stock Items or $60 Addl Schneider Handling Fee Applies
This standard MX shunt trip is used on Compact NSXm and PowerPact B devices. This auxiliary is used for emergency off or failsafe remote opening applications. It is a one click spring type auxiliary for quick and easy installation, visible from the front face of the device. This MX auxiliary has a 48 VAC 50/60Hz or 48VDC rated voltage. It trips the circuit breaker when the control voltage rises above 70% of its rated value. It complies with IEC 60947-2 standard. Compact NSXm and PowerPact B embed either 1 MN or 1 MX coil.
- Eu Rohs Directive:
- Compliant with Exemptions
- [Uc] Control Circuit Voltage:
- 48 V AC 50/60 Hz || 48 V DC
- Device Application:
- control
- Voltage Release Type:
- opening coil || shunt trip release
- Control Signal Type:
- maintained || impulse
- Device Short Name:
- MX
- Product Or Component Type:
- voltage release
- Sustainable Offer Status:
- Green Premium product
- Environmental Disclosure:
- ENVPEP2311043EN
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Mercury Free:
- Yes
- Response Time:
- < 50 ms
- Range Compatibility:
- ComPact ComPacT NSXm new generation || ComPact ComPact NSXm || PowerPact PowerPact B
- Circularity Profile:
- ENVEOLI2311043EN
- Range Of Product:
- ComPacT NSXm new generation
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Range:
- ComPact
- Rohs Exemption Information:
- Yes
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Control Type:
- standard
- Impulse Duration:
- >= 20 ms
- Auxiliary Connection Terminal:
- spring
- Threshold Tripping Voltage:
- 0.7 Un opening
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Brochure:
- View
- Datasheet:
- View