- Device Short Name:
- N40 Vigi
- Height:
- 81 mm
- Neutral Position:
- left
- Mechanical Durability:
- 20000 cycles
- Earth-Leakage Protection Class:
- type AC
- Circularity Profile:
- ENVEOLI2306032
- Magnetic Tripping Limit:
- 8.5 x In +/- 20 % AC
- Eu Rohs Directive:
- Compliant with Exemptions
- Provision For Padlocking:
- padlockable
- Wire Stripping Length:
- 13 mm for top or bottom connection
- Electromagnetic Compatibility:
- 8/20 µs impulse withstand, 250 A
- Earth-Leakage Protection:
- integrated
- Earth-Leakage Sensitivity:
- 30 mA
- Color:
- Gray
- Breaking Capacity:
- 6 kA Icu 240 V AC 50 Hz EN/IEC 60947-2 || 6000 A Icn 240 V AC 50 Hz EN/IEC 61009-1
- Standards:
- EN/IEC 61009-1 || EN/IEC 60947-2
- Number Of Protected Poles:
- 1
- Control Type:
- toggle
- Relative Humidity:
- 95-95 % 55-55 °C
- [Ue] Rated Operational Voltage:
- 240 V AC 50 Hz
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- 9 Mm Pitches:
- 4
- Surge Current:
- 250 A
- Poles Description:
- 1P + N
- Residual Current Tripping Technology:
- voltage independent
- Product Or Component Type:
- residual current breaker with overcurrent protection (RCBO)
- Connection Pitch:
- 9 mm between phase and neutral
- Tropicalisation:
- 2 IEC 60068-1
- Halogen Content Performance:
- Halogen free plastic parts product
- Environmental Disclosure:
- ENVPEP2306032EN
- Network Frequency:
- 50 Hz
- Contact Position Indicator:
- yes
- Product Name:
- Multi9 N40 Vigi
- Utilisation Category:
- category A EN/IEC 60947-2
- Sustainable Offer Status:
- Green Premium product
- [Ics] Rated Service Breaking Capacity:
- 4.5 kA 75 % EN/IEC 60947-2 - 240 V AC 50 Hz
- Connections - Terminals:
- tunnel type terminal top or bottom) 0.75-16 mm² - rigid || tunnel type terminal top or bottom) 0.33-10 mm² - flexible || tunnel type terminal top or bottom) 0.33-10 mm² - flexible with ferrule
- Local Signalling:
- fault indication || ON/OFF indication
- Electrical Durability:
- 20000 cycles
- Earth-Leakage Protection Time Delay:
- instantaneous
- Mercury Free:
- Yes
- Limitation Class:
- 3 EN/IEC 61009-1
- Suitability For Isolation:
- yes EN/IEC 60947-2
- Device Application:
- distribution
- [Uimp] Rated Impulse Withstand Voltage:
- 4 kVEN/IEC 60947-2
- Pollution Degree:
- 3 EN/IEC 60947-2
- Rohs Exemption Information:
- Yes
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Depth:
- 70 mm
- Ip Degree Of Protection:
- IP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
- Tightening Torque:
- 2-2 N.m top or bottom
- [Ui] Rated Insulation Voltage:
- 400 V AC 50 Hz EN/IEC 60947-2
- Line Rated Current:
- 10 A 50 °C EN/IEC 60947-2
- Rated Breaking And Making Capacity:
- Idm 4500 A 240 V AC 50 Hz EN/IEC 61009-1
- Net Weight:
- 0.125 kg
- Curve Code:
- C
- Ambient Air Temperature For Storage:
- -30-70 °C
- Ambient Air Temperature For Operation:
- -5-60 °C
- Width:
- 36 mm
- Overvoltage Category:
- IV
- Trip Unit Technology:
- thermal-magnetic
- Range:
- Multi9
- Network Type:
- AC
- Mounting Support:
- DIN rail
- Mounting Mode:
- clip-on
- QN-QUOTE-REQUEST: