Schneider Electric M9U31225 Multi9 C60H-Dc 2P 25A D 10Ka 500V-Dc Mcb
Schneider Electric
$392.00
$1200 Minimum Order for Non-stock Items or $60 Addl Schneider Handling Fee Applies
This Multi9 C60H-DC is a low voltage miniature circuit breaker (MCB) dedicated to direct current. It is a 2P circuit breaker with 2 protected poles, 25A rated current and D tripping curve. The rated short circuit breaking capacity goes up to 20kA at 220VDC conforming to EN/IEC 60947-2 standard and 20kA at 220VDC conforming to EN/IEC 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. It has been designed to offer enhanced protection by preventing, protecting people and equipment from electrical threats. This product protects from short circuit, earth leakage and overload. This product is dedicated for original equipment manufacturers (OEM) and control panel builders. It has an electrical endurance going up to 3000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 220VDC. The Ui rated insulation voltage is 500VDC. The Uimp rated impulse withstand voltage is 6kV. The product can be clipped on a DIN rail. Its width is 4 pitches of 9mm. Pollution degree is 3. The product colour is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 73mm. The weight is 0.128kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -25°C to 70°C. The storage temperature is -40°C to 85°C.
- Network Type:
- DC
- Mounting Support:
- DIN rail
- Product Name:
- Multi9 C60H-DC
- [Ics] Rated Service Breaking Capacity:
- 7.5 kA 75 % EN/IEC 60947-2 - 440 V DC || 4.5 kA 75 % EN/IEC 60947-2 - 500 V DC || 15 kA 75 % EN/IEC 60947-2 - 220 V DC || 7.5 kA 75 % GB 14048.2 - 440 V DC || 4.5 kA 75 % GB 14048.2 - 500 V DC || 15 kA 75 % GB 14048.2 - 220 V DC
- Breaking Capacity:
- 20 kA Icu 220 V DC EN/IEC 60947-2 || 10 kA Icu 440 V DC EN/IEC 60947-2 || 6 kA Icu 500 V DC EN/IEC 60947-2 || 5 kA AIR 12...500 V DC UL 1077 || 20 kA Icu 220 V DC GB 14048.2 || 10 kA Icu 440 V DC GB 14048.2 || 6 kA Icu 500 V DC GB 14048.2
- Width:
- 36 mm
- Tropicalisation:
- 2 IEC 60068-2 || 2 GB 14048.2
- Relative Humidity:
- 95-95 % 55-55 °C
- Wire Stripping Length:
- 14 mm for top or bottom connection
- Environmental Disclosure:
- ENVPEP2308050EN
- Device Short Name:
- C60H-DC
- Range:
- Multi9
- Ip Degree Of Protection:
- IP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
- Net Weight:
- 0.128 kg
- Tightening Torque:
- 3.5-3.5 N.m top or bottom
- Suitability For Isolation:
- yes EN/IEC 60947-2
- Height:
- 81 mm
- Circularity Profile:
- N/A
- Mercury Free:
- Yes
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- [Ue] Rated Operational Voltage:
- 220 V DC || 440 V DC || 500 V DC
- Magnetic Tripping Limit:
- 10...14 x In DC
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kVEN/IEC 60947-2
- Number Of Protected Poles:
- 2
- 9 Mm Pitches:
- 4
- Earth-Leakage Protection:
- without
- Ambient Air Temperature For Storage:
- -40-85 °C
- Ambient Air Temperature For Operation:
- -25-70 °C
- Eu Rohs Directive:
- Compliant
- Sustainable Offer Status:
- Green Premium product
- Connections - Terminals:
- tunnel type terminal top or bottom) 1-35 mm² AWG 18...AWG 2) - rigid stranded || tunnel type terminal top or bottom) 1-25 mm² AWG 18...AWG 4) - flexible || tunnel type terminal top or bottom) 1-25 mm² AWG 18...AWG 4) - flexible with ferrule || tun
- Product Certifications:
- IEC || CCC || UR
- Electrical Durability:
- 3000 cycles 250 V DC L/R = 2 ms || 6000 cycles 250 V DC
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Heat Dissipation:
- 6.2-6.2 W 440 V - 25 A
- Local Signalling:
- ON/OFF indication
- Pollution Degree:
- 3 EN/IEC 60947-2
- Control Type:
- toggle
- Rohs Exemption Information:
- Yes
- Trip Unit Technology:
- thermal-magnetic
- [Ui] Rated Insulation Voltage:
- 500 V DC EN/IEC 60947-2
- Mounting Mode:
- clip-on
- Curve Code:
- D
- Line Rated Current:
- 25 A 25 °C EN/IEC 60947-2
- Standards:
- EN/IEC 60947-2 || GB 14048.2 || UL 1077
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Contact Position Indicator:
- yes
- Device Application:
- distribution
- Poles Description:
- 2P
- Depth:
- 73 mm
- Product Or Component Type:
- miniature circuit-breaker
- Color:
- Gray
- Provision For Padlocking:
- padlockable
- Toxic Heavy Metal Free:
- Yes
- Utilisation Category:
- category A EN/IEC 60947-2
- Mechanical Durability:
- 20000 cycles
- Brochure:
- View
- Datasheet:
- View