- Circularity Profile:
- ENVEOLI2206030EN
- Depth:
- 8.05 in
- Breaking Capacity Code:
- G
- Ambient Air Temperature For Storage:
- -50-85 °C
- Local Signalling:
- 1 trip indicator green)
- Sustainable Offer Status:
- Green Premium product
- Pollution Degree:
- 3 IEC 60947-1
- Mounting Support:
- lug
- Terminal Identifier:
- AL800M23K
- Quantity Per Set:
- 1
- Poles Description:
- 3P
- Product Certifications:
- UL || CSA || NOM
- Product Name:
- PowerPact M
- Eu Rohs Directive:
- Compliant with Exemptions
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Pvc Free:
- Yes
- Device Application:
- distribution
- Trip Unit Technology:
- electronic, basic, ET 1.0,
- Continuous Current Rating:
- 0.8
- Wire Stripping Length:
- 25 mm
- Rohs Exemption Information:
- Yes
- Color:
- Black
- Line Rated Current:
- 800-800 A
- Range:
- PowerPact
- Long Time Pick-Up Adjustment Range:
- 300...800 A
- Width:
- 8.27 in
- Mounting Mode:
- unit mount lug)
- Utilisation Category:
- category A
- Control Type:
- operating handle
- Ip Degree Of Protection:
- IP40
- Circuit Breaker Application:
- HACR rated
- Electrical Connection:
- lugs, line || terminal nut, load
- Awg Gauge:
- 3 x AWG 3/0...3 x 500 kcmil aluminium/copper
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Product Or Component Type:
- circuit breaker
- Net Weight:
- 29 lb(US)
- Environmental Disclosure:
- ENVPEP2206030EN
- Mercury Free:
- Yes
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Suitability For Isolation:
- yes IEC 60947-2
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Height:
- 12.86 in
- Trip Unit Name:
- ET 1.0
- Warranty:
- 18 months
- Quality Labels:
- CE
- Magnetic Tripping Current:
- 1600-8000 A
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...3 x 500 kcmil)
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Network Frequency:
- 50/60 Hz
- Ambient Air Temperature For Operation:
- -25-70 °C
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489