- Depth:
- 8.05 in
- Pvc Free:
- Yes
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Quality Labels:
- CE
- Product Certifications:
- UL || CSA || NOM
- Local Signalling:
- 1 trip indicator green)
- Line Rated Current:
- 400-400 A
- Pollution Degree:
- 3 IEC 60947-1
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Long Time Pick-Up Adjustment Range:
- 300...800 A
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Trip Unit Name:
- ET 1.0
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Eu Rohs Directive:
- Compliant with Exemptions
- Range:
- PowerPact
- Product Or Component Type:
- circuit breaker
- Net Weight:
- 29 lb(US)
- Warranty:
- 18 months
- Utilisation Category:
- category A
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Trip Unit Technology:
- electronic, basic, ET 1.0,
- Mounting Mode:
- unit mount lug)
- Circularity Profile:
- ENVEOLI2206030EN
- Suitability For Isolation:
- yes IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Electrical Connection:
- terminal nut, line || lugs, load
- Mounting Support:
- lug
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Breaking Capacity Code:
- G
- Sustainable Offer Status:
- Green Premium product
- Width:
- 8.27 in
- Height:
- 12.86 in
- Magnetic Tripping Current:
- 800-4000 A
- Wire Stripping Length:
- 25 mm
- Continuous Current Rating:
- 0.8
- Environmental Disclosure:
- ENVPEP2206030EN
- Poles Description:
- 3P
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Device Application:
- distribution
- Ambient Air Temperature For Operation:
- -25-70 °C
- Product Name:
- PowerPact M
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Quantity Per Set:
- 1
- Terminal Identifier:
- AL800M23K
- Awg Gauge:
- 3 x AWG 3/0...3 x 500 kcmil aluminium/copper
- Mercury Free:
- Yes
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Color:
- Black
- Network Frequency:
- 50/60 Hz
- Ambient Air Temperature For Storage:
- -50-85 °C
- Rohs Exemption Information:
- Yes
- Control Type:
- operating handle
- Ip Degree Of Protection:
- IP40
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...3 x 500 kcmil)