- Sustainable Offer Status:
- Green Premium product
- Trip Unit Technology:
- electronic, basic, ET 1.0,
- Ambient Air Temperature For Storage:
- -50-85 °C
- Circuit Breaker Application:
- HACR rated
- Ambient Air Temperature For Operation:
- -25-70 °C
- Mounting Support:
- busbar
- Product Or Component Type:
- circuit breaker
- Depth:
- 8.05 in
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Mounting Mode:
- unit mount busbar)
- Long Time Pick-Up Adjustment Range:
- 300...800 A
- Width:
- 8.27 in
- Awg Gauge:
- 3 x AWG 3/0...3 x 500 kcmil aluminium/copper
- Ip Degree Of Protection:
- IP40
- Range:
- PowerPact
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Magnetic Tripping Current:
- 1600-8000 A
- Utilisation Category:
- category A
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Quality Labels:
- CE
- Circularity Profile:
- ENVEOLI2206030EN
- Accessory / Separate Part Type:
- communication module
- Product Certifications:
- UL || CSA || NOM
- Poles Description:
- 3P
- Terminal Identifier:
- AL800M23K
- Communication Interface:
- Modbus
- Pollution Degree:
- 3 IEC 60947-1
- Height:
- 12.86 in
- Net Weight:
- 29 lb(US)
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...3 x 500 kcmil)
- Local Signalling:
- 1 trip indicator green)
- Device Application:
- distribution
- Network Frequency:
- 50/60 Hz
- Wire Stripping Length:
- 25 mm
- Line Rated Current:
- 300-800 A
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Rohs Exemption Information:
- Yes
- Mercury Free:
- Yes
- Environmental Disclosure:
- ENVPEP2206030EN
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Electrical Connection:
- busbar connection, line || busbar connection, load
- Suitability For Isolation:
- yes IEC 60947-2
- Quantity Per Set:
- 1
- Product Name:
- PowerPact M
- Color:
- Black
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Trip Unit Name:
- ET 1.0
- Breaking Capacity Code:
- J
- Control Type:
- operating handle
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Pvc Free:
- Yes
- Eu Rohs Directive:
- Compliant with Exemptions
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Continuous Current Rating:
- 0.8