- Poles Description:
- 3P
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Long Time Pick-Up Adjustment Range:
- 0.4...1 x Ir
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Pvc Free:
- Yes
- Product Name:
- PowerPact P
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Awg Gauge:
- 3 x AWG 3/0...500 kcmil aluminium/copper
- Product Or Component Type:
- circuit breaker
- Depth:
- 8.05 in
- Height:
- 12.86 in
- Electrical Connection:
- lugs, load || lugs, line
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Terminal Identifier:
- AL800M23K
- Control Type:
- toggle
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Network Frequency:
- 50/60 Hz
- Circularity Profile:
- ENVEOLI2206033EN
- Warranty:
- 18 months
- Mercury Free:
- Yes
- Width:
- 8.27 in
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Environmental Disclosure:
- ENVPEP2206033EN
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
- Wire Stripping Length:
- 25 mm
- Net Weight:
- 32 lb(US)
- Ambient Air Temperature For Operation:
- -2-70 °C
- Pollution Degree:
- 3 IEC 60947-1
- Ip Degree Of Protection:
- front cover IP40
- Trip Unit Technology:
- electronic, standard, MicroLogic 5.0, LSI
- Ambient Air Temperature For Storage:
- -50-85 °C
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Breaking Capacity Code:
- G
- Device Application:
- distribution
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Circuit Breaker Application:
- HACR rated
- Trip Unit Name:
- MicroLogic 5.0
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Continuous Current Rating:
- 0.8
- Rohs Exemption Information:
- Yes
- Quantity Per Set:
- 1
- Quality Labels:
- CE
- Line Rated Current:
- 800-800 A
- Local Signalling:
- overload 1 1 LED amber) || 1 trip indicator green)
- Eu Rohs Directive:
- Compliant with Exemptions
- Sustainable Offer Status:
- Green Premium product
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Product Certifications:
- UL || CSA || NOM
- Range:
- PowerPact