Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Ambient Air Temperature For Operation:
-2-70 °C
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Depth:
8.05 in
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Sustainable Offer Status:
Green Premium product
Pvc Free:
Yes
Product Certifications:
UL || CSA || NOM
Eu Rohs Directive:
Compliant with Exemptions
Wire Stripping Length:
30 mm
Control Type:
toggle
Terminal Identifier:
AL1200P25K
Continuous Current Rating:
1
Poles Description:
3P
Range:
PowerPact
Height:
16.16 in
Trip Unit Technology:
electronic, power, MicroLogic 5.0 P, LSI
Communication Interface:
Modbus
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Pollution Degree:
3 IEC 60947-1
Electrical Connection:
lugs, load || lugs, line
Quantity Per Set:
1
Trip Unit Name:
MicroLogic 5.0 P
Long Time Pick-Up Adjustment Range:
0.4...1 x Ir
Local Signalling:
1 trip indicator green)
Ambient Air Temperature For Storage:
-50-85 °C
Accessory / Separate Part Type:
Modbus connecting cable
Warranty:
18 months
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz UL 489
Device Application:
distribution
Breaking Capacity Code:
G
Breaking Capacity:
AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
Circularity Profile:
ENVEOLI2206033EN
Mercury Free:
Yes
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Environmental Disclosure:
ENVPEP2206033EN
Product Name:
PowerPact P
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Ip Degree Of Protection:
front cover IP40
Width:
8.27 in
Line Rated Current:
1200-1200 A
Awg Gauge:
4 x AWG 3/0...500 kcmil aluminium/copper
Tightening Torque:
50-50 N.m 95-240 mm² (4 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
Product Or Component Type:
circuit breaker
[Ics] Rated Service Breaking Capacity:
25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
Rohs Exemption Information:
Yes
Quality Labels:
CE
Circuit Breaker Application:
HACR rated
Network Frequency:
50/60 Hz
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Net Weight:
32 lb(US)
Brochure:
View
Catalog:
View
Datasheet:
View
  • Schneider Electric PGL36120CU63AE1 Molded Case Circuit Breaker 600V 1200A
  • Schneider Electric PGL36120CU63AE1 Molded Case Circuit Breaker 600V 1200A
$36,243.00

Description

PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has a Micrologic Interchangeable Power with a 5.0P trip unit and an LSI function with Modbus communications. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has lugs on both the line and load sides. This PowerPacT P, 1200A, 3 pole, circuit breaker has an interrupting rating of 18kA at 600VAC. This circuit breaker has a continuous current rating of 100%. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.