Tightening Torque:
50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
Depth:
8.05 in
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Long Time Pick-Up Adjustment Range:
0.4...1 x Ir
Mounting Support:
bracket
Continuous Current Rating:
0.8
Product Name:
PowerPact P
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Mounting Mode:
I-Line bracket)
Quality Labels:
CE
Ambient Air Temperature For Operation:
-2-70 °C
Line Rated Current:
600-600 A
Warranty:
18 months
Mercury Free:
Yes
Breaking Capacity Code:
J
Range:
PowerPact
Quantity Per Set:
1
Terminal Identifier:
AL800M23K
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Network Frequency:
50/60 Hz
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Device Application:
distribution
Product Or Component Type:
circuit breaker
Trip Unit Technology:
electronic, standard, MicroLogic 3.0, LI
Mounting Height:
9 in
Net Weight:
32 lb(US)
Circularity Profile:
ENVEOLI2206033EN
Pollution Degree:
3 IEC 60947-1
Ambient Air Temperature For Storage:
-50-85 °C
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Ip Degree Of Protection:
front cover IP40
Eu Rohs Directive:
Compliant with Exemptions
Phase Connection:
ABC
Poles Description:
3P
Breaking Capacity:
AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
Pvc Free:
Yes
[Ics] Rated Service Breaking Capacity:
35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
Wire Stripping Length:
25 mm
Control Type:
toggle
Height:
12.86 in
Width:
8.27 in
Circuit Breaker Application:
HACR rated
Local Signalling:
1 trip indicator green)
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Awg Gauge:
3 x AWG 3/0...500 kcmil aluminium/copper
Sustainable Offer Status:
Green Premium product
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Trip Unit Name:
MicroLogic 3.0
Product Certifications:
UL || CSA || NOM
Rohs Exemption Information:
Yes
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz UL 489
Environmental Disclosure:
ENVPEP2206033EN
Electrical Connection:
I-Line connection, line || lugs, load
Brochure:
View
Catalog:
View
Datasheet:
View
  • Schneider Electric PJA36060U31A Molded Case Circuit Breaker 600V 600A
  • Schneider Electric PJA36060U31A Molded Case Circuit Breaker 600V 600A
$16,268.00

Description

PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has a Micrologic Interchangeable Standard with a 3.0 trip unit and an LI function. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT P, 600A, 3 pole, circuit breaker has an interrupting rating of 25kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose