- Phase Connection:
- ABC
- Trip Unit Name:
- MicroLogic 6.0 A
- Pollution Degree:
- 3 IEC 60947-1
- Mercury Free:
- Yes
- Rohs Exemption Information:
- Yes
- Network Frequency:
- 50/60 Hz
- Environmental Disclosure:
- ENVPEP2206033EN
- Mounting Support:
- bracket
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Poles Description:
- 3P
- Electrical Connection:
- I-Line connection, line || lugs, load
- Continuous Current Rating:
- 0.8
- Product Certifications:
- UL || CSA || NOM
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Control Type:
- toggle
- Ip Degree Of Protection:
- front cover IP40
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Breaking Capacity Code:
- J
- Pvc Free:
- Yes
- Quantity Per Set:
- 1
- Mounting Height:
- 9 in
- Warranty:
- 18 months
- Product Or Component Type:
- circuit breaker
- Circuit Breaker Application:
- HACR rated
- Width:
- 8.27 in
- Device Application:
- distribution
- Awg Gauge:
- 3 x AWG 3/0...500 kcmil aluminium/copper
- Eu Rohs Directive:
- Compliant with Exemptions
- Circularity Profile:
- ENVEOLI2206033EN
- Line Rated Current:
- 600-600 A
- Depth:
- 8.05 in
- Quality Labels:
- CE
- Product Name:
- PowerPact P
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Terminal Identifier:
- AL800M23K
- Sustainable Offer Status:
- Green Premium product
- Mounting Mode:
- I-Line bracket)
- Local Signalling:
- 1 trip indicator green)
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 6.0 A, LSIG
- Height:
- 12.86 in
- Net Weight:
- 32 lb(US)
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Long Time Pick-Up Adjustment Range:
- 0.4...1 x Ir
- Wire Stripping Length:
- 25 mm
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Range:
- PowerPact
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Ambient Air Temperature For Operation:
- -2-70 °C
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Ambient Air Temperature For Storage:
- -50-85 °C
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- QN-QUOTE-REQUEST:
- true