- Height:
- 16.16 in
- Product Certifications:
- UL || CSA || NOM
- Quality Labels:
- CE
- Long Time Pick-Up Adjustment Range:
- 0.4...1 x Ir
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Quantity Per Set:
- 1
- Pvc Free:
- Yes
- Mounting Height:
- 9 in
- Eu Rohs Directive:
- Compliant with Exemptions
- Net Weight:
- 32 lb(US)
- Wire Stripping Length:
- 30 mm
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Line Rated Current:
- 1200-1200 A
- Device Application:
- distribution
- Tightening Torque:
- 50-50 N.m 95-240 mm² (4 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
- Sustainable Offer Status:
- Green Premium product
- Continuous Current Rating:
- 0.8
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Trip Unit Name:
- MicroLogic 3.0
- Environmental Disclosure:
- ENVPEP2206033EN
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Control Type:
- toggle
- Network Frequency:
- 50/60 Hz
- Product Name:
- PowerPact P
- Ip Degree Of Protection:
- front cover IP40
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Mounting Mode:
- I-Line bracket)
- Range:
- PowerPact
- Ambient Air Temperature For Operation:
- -2-70 °C
- Mercury Free:
- Yes
- Local Signalling:
- overload 1 1 LED amber) || 1 trip indicator green)
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Terminal Identifier:
- AL1200P25K
- Rohs Exemption Information:
- Yes
- Awg Gauge:
- 4 x AWG 3/0...500 kcmil aluminium/copper
- Poles Description:
- 3P
- Mounting Support:
- bracket
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.0, LI
- Depth:
- 8.05 in
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Product Or Component Type:
- circuit breaker
- Circuit Breaker Application:
- HACR rated
- Pollution Degree:
- 3 IEC 60947-1
- Electrical Connection:
- I-Line connection, line || lugs, load
- Phase Connection:
- ABC
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Width:
- 8.27 in
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Warranty:
- 18 months
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Ambient Air Temperature For Storage:
- -50-85 °C
- Circularity Profile:
- ENVEOLI2206033EN
- Breaking Capacity Code:
- J
- QN-QUOTE-REQUEST: