Schneider Electric

Schneider Electric PJL36060CU31A Molded Case Circuit Breaker 600V 600A

(No reviews yet) Write a Review
SKU:
PJL36060CU31A
UPC:
785901982616
Condition:
New
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Range:
PowerPact
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz UL 489
Quantity Per Set:
1
Line Rated Current:
600-600 A
Trip Unit Name:
MicroLogic 3.0
Mounting Support:
lug
Breaking Capacity:
AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Trip Unit Technology:
electronic, standard, MicroLogic 3.0, LI
Pvc Free:
Yes
Ambient Air Temperature For Storage:
-50-85 °C
Ambient Air Temperature For Operation:
-2-70 °C
Width:
8.27 in
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Network Frequency:
50/60 Hz
Device Application:
distribution
Terminal Identifier:
AL800M23K
Mounting Mode:
unit mount lug)
Breaking Capacity Code:
J
Circuit Breaker Application:
HACR rated
Control Type:
toggle
Ip Degree Of Protection:
front cover IP40
Continuous Current Rating:
1
Warranty:
18 months
Long Time Pick-Up Adjustment Range:
0.4...1 x Ir
Pollution Degree:
3 IEC 60947-1
Wire Stripping Length:
25 mm
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Circularity Profile:
ENVEOLI2206033EN
Depth:
8.05 in
Net Weight:
32 lb(US)
Product Or Component Type:
circuit breaker
Electrical Connection:
lugs, line || lugs, load
Product Name:
PowerPact P
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Sustainable Offer Status:
Green Premium product
Rohs Exemption Information:
Yes
Local Signalling:
overload 1 trip indicator green) || 1 trip indicator green)
Awg Gauge:
3 x AWG 3/0...500 kcmil aluminium/copper
Environmental Disclosure:
ENVPEP2206033EN
Eu Rohs Directive:
Compliant with Exemptions
Poles Description:
3P
Product Certifications:
UL || CSA || NOM
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Quality Labels:
CE
Mercury Free:
Yes
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Height:
12.86 in
[Ics] Rated Service Breaking Capacity:
35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Tightening Torque:
50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
Brochure:
View
Catalog:
View
Datasheet:
View
$22,868.00

Description

PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has a Micrologic Interchangeable Standard with a 3.0 trip unit and an LI function. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has lugs on both the line and load sides. This PowerPacT P, 600A, 3 pole, circuit breaker has an interrupting rating of 25kA at 600VAC. This circuit breaker has a continuous current rating of 100%. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose