- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Awg Gauge:
- 3 x AWG 3/0...500 kcmil aluminium/copper
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Control Type:
- toggle
- Pollution Degree:
- 3 IEC 60947-1
- Ambient Air Temperature For Operation:
- -2-70 °C
- Mounting Mode:
- unit mount lug)
- Poles Description:
- 3P
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
- Circuit Breaker Application:
- HACR rated
- Mercury Free:
- Yes
- Continuous Current Rating:
- 1
- Trip Unit Technology:
- electronic, standard, MicroLogic 5.0, LSI
- Long Time Pick-Up Adjustment Range:
- 0.4...1 x Ir
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Product Or Component Type:
- circuit breaker
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Ip Degree Of Protection:
- front cover IP40
- Depth:
- 8.05 in
- Quality Labels:
- CE
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Rohs Exemption Information:
- Yes
- Local Signalling:
- overload 1 trip indicator green) || 1 trip indicator green)
- Height:
- 12.86 in
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile:
- ENVEOLI2206033EN
- Environmental Disclosure:
- ENVPEP2206033EN
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Pvc Free:
- Yes
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Quantity Per Set:
- 1
- Electrical Connection:
- lugs, line || lugs, load
- Product Name:
- PowerPact P
- Sustainable Offer Status:
- Green Premium product
- Eu Rohs Directive:
- Compliant with Exemptions
- Network Frequency:
- 50/60 Hz
- Width:
- 8.27 in
- Terminal Identifier:
- AL800M23K
- Net Weight:
- 32 lb(US)
- Trip Unit Name:
- MicroLogic 5.0
- Ambient Air Temperature For Storage:
- -50-85 °C
- Product Certifications:
- UL || CSA || NOM
- Breaking Capacity Code:
- J
- Mounting Support:
- lug
- Range:
- PowerPact
- Line Rated Current:
- 600-600 A
- Wire Stripping Length:
- 25 mm
- Warranty:
- 18 months
- Device Application:
- distribution
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2