- Product Or Component Type:
- Motor Circuit Protector
- Continuous Current Rating:
- 0.8
- Quality Labels:
- CE
- Ip Degree Of Protection:
- front cover IP40
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Range:
- PowerPact
- Pollution Degree:
- 3 IEC 60947-1
- Pvc Free:
- Yes
- Network Frequency:
- 50/60 Hz
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Control Type:
- toggle
- Electrical Connection:
- lugs, line || lugs, load
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Local Signalling:
- 1 trip indicator green)
- Environmental Disclosure:
- ENVPEP2206033EN
- Device Application:
- distribution
- Terminal Identifier:
- AL800M23K
- Sustainable Offer Status:
- Green Premium product
- Ambient Air Temperature For Storage:
- -50-85 °C
- Net Weight:
- 32 lb(US)
- Trip Unit Technology:
- electronic, basic, ET 1.0, I
- Trip Unit Name:
- ET 1.0
- Depth:
- 8.05 in
- Wire Stripping Length:
- 25 mm
- Quantity Per Set:
- 1
- Mercury Free:
- Yes
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Breaking Capacity Code:
- J
- Awg Gauge:
- 3 x AWG 3/0...500 kcmil aluminium/copper
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Ambient Air Temperature For Operation:
- -2-70 °C
- Mounting Support:
- lug
- Product Name:
- PowerPact P
- Circuit Breaker Application:
- HACR rated
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- [Ith] Conventional Free Air Thermal Current:
- 800-800 A
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Mounting Mode:
- unit mount lug)
- Width:
- 8.27 in
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Rohs Exemption Information:
- Yes
- Warranty:
- 18 months
- Height:
- 12.86 in
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Poles Description:
- 3P
- Eu Rohs Directive:
- Compliant with Exemptions
- Product Certifications:
- UL || CSA || NOM
- Line Rated Current:
- 800-800 A
- Magnetic Tripping Current:
- 1200-10000 A
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
- Circularity Profile:
- ENVEOLI2206033EN