- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Rohs Exemption Information:
- Yes
- Range:
- PowerPact
- Continuous Current Rating:
- 0.8
- Sustainable Offer Status:
- Green Premium product
- Awg Gauge:
- 3 x AWG 3/0...500 kcmil aluminium/copper
- Product Or Component Type:
- circuit breaker
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Circularity Profile:
- ENVEOLI2206033EN
- Ip Degree Of Protection:
- front cover IP40
- Device Application:
- distribution
- Eu Rohs Directive:
- Compliant with Exemptions
- Height:
- 12.86 in
- Line Rated Current:
- 800-800 A
- Width:
- 8.27 in
- Trip Unit Name:
- MicroLogic 3.0
- Mounting Mode:
- unit mount lug)
- Ambient Air Temperature For Storage:
- -50-85 °C
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Pvc Free:
- Yes
- Ambient Air Temperature For Operation:
- -2-70 °C
- Net Weight:
- 32 lb(US)
- Breaking Capacity Code:
- J
- Warranty:
- 18 months
- Quantity Per Set:
- 1
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Poles Description:
- 3P
- Product Certifications:
- UL || CSA || NOM
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Depth:
- 8.05 in
- Mounting Support:
- lug
- Network Frequency:
- 50/60 Hz
- Mercury Free:
- Yes
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
- Pollution Degree:
- 3 IEC 60947-1
- Quality Labels:
- CE
- Long Time Pick-Up Adjustment Range:
- 0.4...1 x Ir
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Local Signalling:
- overload 1 1 LED amber) || 1 trip indicator green)
- Circuit Breaker Application:
- HACR rated
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.0, LI
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Terminal Identifier:
- AL800M23K
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Electrical Connection:
- lugs, line || lugs, load
- Control Type:
- toggle
- Environmental Disclosure:
- ENVPEP2206033EN
- Wire Stripping Length:
- 25 mm
- Product Name:
- PowerPact P