- Rohs Exemption Information:
- Yes
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Product Name:
- PowerPact P
- Sustainable Offer Status:
- Green Premium product
- Quality Labels:
- CE
- Mounting Support:
- lug
- Height:
- 16.16 in
- Continuous Current Rating:
- 0.8
- Line Rated Current:
- 1000-1000 A
- Ambient Air Temperature For Storage:
- -50-85 °C
- Mercury Free:
- Yes
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Quantity Per Set:
- 1
- Control Type:
- toggle
- Warranty:
- 18 months
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Network Frequency:
- 50/60 Hz
- Pollution Degree:
- 3 IEC 60947-1
- Awg Gauge:
- 4 x AWG 3/0...500 kcmil aluminium/copper
- Circularity Profile:
- ENVEOLI2206033EN
- Poles Description:
- 3P
- Terminal Identifier:
- AL1200P25K
- Range:
- PowerPact
- Long Time Pick-Up Adjustment Range:
- 0.4...1 x Ir
- Trip Unit Name:
- MicroLogic 6.0 A
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 6.0 A, LSIG
- Electrical Connection:
- lugs, line || lugs, load
- Wire Stripping Length:
- 30 mm
- Local Signalling:
- overload 1 trip indicator green) || 1 trip indicator green) || trip causes 1 trip indicator green)
- Circuit Breaker Application:
- HACR rated
- Ambient Air Temperature For Operation:
- -2-70 °C
- Eu Rohs Directive:
- Compliant with Exemptions
- Mounting Mode:
- unit mount lug)
- Net Weight:
- 32 lb(US)
- Device Application:
- distribution
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Pvc Free:
- Yes
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Width:
- 8.27 in
- Product Or Component Type:
- circuit breaker
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Tightening Torque:
- 50-50 N.m 95-240 mm² (4 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
- Suitability For Isolation:
- yes IEC 60947-2
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Utilisation Category:
- category A
- Ip Degree Of Protection:
- front cover IP40
- Environmental Disclosure:
- ENVPEP2206033EN
- Depth:
- 8.05 in
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Breaking Capacity Code:
- J