Schneider Electric

Schneider Electric PJL36120U31A Molded Case Circuit Breaker 600V 1200A

(No reviews yet) Write a Review
SKU:
PJL36120U31A
UPC:
7.85902E+11
Condition:
New
Ambient Air Temperature For Operation:
-2-70 °C
Suitability For Isolation:
yes IEC 60947-2
Trip Unit Name:
MicroLogic 3.0
Width:
8.27 in
Mounting Support:
lug
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
[Ics] Rated Service Breaking Capacity:
35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
Mounting Mode:
unit mount lug)
Rohs Exemption Information:
Yes
Range:
PowerPact
Pvc Free:
Yes
Product Certifications:
UL || CSA || NOM
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Continuous Current Rating:
0.8
Long Time Pick-Up Adjustment Range:
0.4...1 x Ir
Product Name:
PowerPact P
Net Weight:
32 lb(US)
Electrical Connection:
lugs, line || lugs, load
Eu Rohs Directive:
Compliant with Exemptions
Warranty:
18 months
Network Frequency:
50/60 Hz
Terminal Identifier:
AL1200P25K
Quality Labels:
CE
Height:
16.16 in
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Product Or Component Type:
circuit breaker
Local Signalling:
overload 1 1 LED amber) || 1 trip indicator green)
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz UL 489
Quantity Per Set:
1
Ip Degree Of Protection:
front cover IP40
Breaking Capacity Code:
J
Depth:
8.05 in
Ambient Air Temperature For Storage:
-50-85 °C
Poles Description:
3P
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Control Type:
toggle
Tightening Torque:
50-50 N.m 95-240 mm² (4 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
Circularity Profile:
ENVEOLI2206033EN
Breaking Capacity:
AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
Line Rated Current:
1200-1200 A
Circuit Breaker Application:
HACR rated
Pollution Degree:
3 IEC 60947-1
Mercury Free:
Yes
Sustainable Offer Status:
Green Premium product
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Wire Stripping Length:
30 mm
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Trip Unit Technology:
electronic, standard, MicroLogic 3.0, LI
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Device Application:
distribution
Environmental Disclosure:
ENVPEP2206033EN
Awg Gauge:
4 x AWG 3/0...500 kcmil aluminium/copper
Utilisation Category:
category A
Brochure:
View
Catalog:
View
Datasheet:
View
$21,038.00

Description

PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has a Micrologic Interchangeable Standard with a 3.0 trip unit and an LI function. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has lugs on both the line and load sides. This PowerPacT P, 1200A, 3 pole, circuit breaker has an interrupting rating of 25kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose