Schneider Electric PJL36120U64AE1 Molded Case Circuit Breaker 600V 1200A
Schneider Electric
$28,881.00
PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has a Micrologic Interchangeable Power with a 6.0P trip unit and an LSIG function with Modbus communications. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has lugs on both the line and load sides. This PowerPacT P, 1200A, 3 pole, circuit breaker has an interrupting rating of 25kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
- Product Or Component Type:
- circuit breaker
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Eu Rohs Directive:
- Compliant with Exemptions
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Height:
- 16.16 in
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Sustainable Offer Status:
- Green Premium product
- Circularity Profile:
- ENVEOLI2206033EN
- Trip Unit Technology:
- electronic, power, MicroLogic 6.0 P, LSI
- Mounting Support:
- lug
- Awg Gauge:
- 4 x AWG 3/0...500 kcmil aluminium/copper
- Accessory / Separate Part Type:
- Modbus connecting cable
- Ip Degree Of Protection:
- front cover IP40
- Depth:
- 8.05 in
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Electrical Connection:
- lugs, line || lugs, load
- Mercury Free:
- Yes
- Continuous Current Rating:
- 0.8
- Net Weight:
- 32 lb(US)
- Device Application:
- distribution
- Tightening Torque:
- 50-50 N.m 95-240 mm² (4 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
- Terminal Identifier:
- AL1200P25K
- Communication Interface:
- Modbus
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Ambient Air Temperature For Operation:
- -2-70 °C
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Product Name:
- PowerPact P
- Local Signalling:
- overload 1 1 LED amber) || 1 flag green) || trip causes 4 trip indicator red)
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Utilisation Category:
- category A
- Poles Description:
- 3P
- Width:
- 8.27 in
- Mounting Mode:
- unit mount lug)
- Control Type:
- toggle
- Quantity Per Set:
- 1
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Quality Labels:
- CE
- Ambient Air Temperature For Storage:
- -50-85 °C
- Pvc Free:
- Yes
- Range:
- PowerPact
- Suitability For Isolation:
- yes IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- Environmental Disclosure:
- ENVPEP2206033EN
- Rohs Exemption Information:
- Yes
- Circuit Breaker Application:
- HACR rated
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Pollution Degree:
- 3 IEC 60947-1
- Network Frequency:
- 50/60 Hz
- Long Time Pick-Up Adjustment Range:
- 0.4...1 x Ir
- Wire Stripping Length:
- 30 mm
- Trip Unit Name:
- MicroLogic 6.0 P
- Warranty:
- 18 months
- Breaking Capacity Code:
- J
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Line Rated Current:
- 1200-1200 A
- Brochure:
- View
- Catalog:
- View
- Datasheet: