Continuous Current Rating:
0.8
Terminal Identifier:
AL1200P25K
Product Or Component Type:
circuit breaker
Ip Degree Of Protection:
front cover IP40
Circularity Profile:
ENVEOLI1407012EN
Poles Description:
3P
Trip Unit Technology:
electronic, basic, ET 1.0I, I
Width:
8.27 in
Quantity Per Set:
1
Net Weight:
32 lb(US)
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Local Signalling:
1 trip indicator green)
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Ambient Air Temperature For Operation:
-2-70 °C
Breaking Capacity Code:
L
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Mercury Free:
Yes
Device Application:
distribution
Depth:
8.05 in
Circuit Breaker Application:
HACR rated
Product Certifications:
UL || CSA || NOM
Tightening Torque:
50-50 N.m 95-240 mm² (4 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Pollution Degree:
3 IEC 60947-1
Mounting Mode:
unit mount lug)
Electrical Connection:
lugs, line || lugs, load
Warranty:
18 months
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Environmental Disclosure:
ENVPEP1407012EN
[Ics] Rated Service Breaking Capacity:
65 kA 240 V AC 50/60 Hz IEC 60947-2 || 45 kA 380/415 V AC 50/60 Hz IEC 60947-2
Network Frequency:
50/60 Hz
Product Name:
PowerPact P
Quality Labels:
CE
Line Rated Current:
1000-1000 A
Wire Stripping Length:
30 mm
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Awg Gauge:
4 x AWG 3/0...500 kcmil aluminium/copper
Trip Unit Name:
ET 1.0I
Control Type:
toggle
Ambient Air Temperature For Storage:
-50-85 °C
Range:
PowerPact
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Eu Rohs Directive:
Compliant
[Ue] Rated Operational Voltage:
480 V AC 50/60 Hz UL 489
Rohs Exemption Information:
Yes
Mounting Support:
lug
Pvc Free:
Yes
Long Time Pick-Up Adjustment Range:
1 In
Breaking Capacity:
AIR 125 kA 240 V AC 50/60 Hz UL 489 || AIR 100 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 125 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 85 kA 380/415 V AC 50/60 Hz IEC 60947-2
Sustainable Offer Status:
Green Premium product
Height:
16.16 in
$21,452.00

Description

PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has an electronic trip unit, ET 1.0I. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has lugs on both the line and load sides. This PowerPacT P, 1000A, 3 pole, circuit breaker has an interrupting rating of 100kA at 480VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.