- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Breaking Capacity:
- 22 kA 120/240 V AC 50/60 Hz || 22 kA 240 V AC 50/60 Hz || 22 kA 120 V AC 50/60 Hz
- [Ue] Rated Operational Voltage:
- 120/240 V AC || 240 V AC || 120 V AC
- Number Of Spaces Required:
- 3
- Eu Rohs Directive:
- Under investigation
- Electrical Connection:
- pressure plate
- Awg Gauge:
- AWG 14...AWG 8 copper or aluminium
- Tightening Torque:
- 4.6-4.6 N.m
- Mounting Mode:
- bolt-on
- Accessory / Separate Part Type:
- shunt trip 12/24 V AC/DC
- Poles Description:
- 2P
- Warranty:
- 18 months
- Height:
- 76 mm
- Range Of Product:
- QO
- Net Weight:
- 0.186 kg
- Line Rated Current:
- 30 A
- Product Certifications:
- UL Listed || CSA
- Depth:
- 74 mm
- Circuit Breaker Type:
- standard
- Width:
- 57 mm
- Product Or Component Type:
- miniature circuit-breaker
- Circuit Breaker Application:
- HACR rated
- Ambient Air Temperature For Operation:
- 40 °C