Schneider Electric RE22R1QCMU Star-Delta Timer Relay
Schneider Electric
$70.35
This Harmony RE22 modular single function timer can be set between 1 seconds and 300 hours." "This modular single function timing relay is ideal for providing timing control in automation systems such as automatic door opening, alarm, lighting in toilets and car park barriers." "It has one of market slimmest form-factors with 22.5mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 2-pole DIN device." "Single function timer for a simple integration in hard-wired logic schematics, ideal for refurbishment of old installations without using a PLC." 0 0 0 0 0 0 0 0 0 0 0 0
- Repeat Accuracy:
- +/- 0.5 % IEC 61812-1
- Device Short Name:
- RE22
- Net Weight:
- 0.08 kg
- Mounting Position:
- any position
- Voltage Range:
- 0.85...1.1 Us
- [Uimp] Rated Impulse Withstand Voltage:
- 5 kV 1.2-50 µs IEC 60664-1
- Pollution Degree:
- 3 IEC 60664-1
- Power Consumption In Va:
- 35-35 VA 240 V AC
- Range Of Product:
- Harmony Timer Relays
- Time Delay Range:
- 10...100 s || 3...30 s || 0.1...1 s || 0.3...3 s || 0.05...0.5 s || 1...10 s || 30...300 s
- Immunity To Microbreaks:
- 10 ms
- Ambient Air Temperature For Storage:
- -40-70 °C
- Maximum Switching Voltage:
- 250 V AC
- Creepage Distance:
- 4 kV/3 IEC 60664-1
- Ambient Air Temperature For Operation:
- -20-60 °C
- Control Type:
- rotary knob || diagnostic button
- Power Consumption In W:
- 0.6 W 24 V DC
- Discrete Output Type:
- relay
- Mounting Support:
- 35 mm DIN rail conforming to IEC 60715
- Mercury Free:
- Yes
- Product Certifications:
- GL || CE || CCC || EAC || UL || CSA || RCM
- Housing Material:
- self-extinguishing
- Safety Reliability Data:
- MTTFd = 285.3 years || B10d = 270000
- Shock Resistance:
- 15 gn not operating 11 ms IEC 60068-2-27 || 5 gn in operation 11 ms IEC 60068-2-27
- Time Delay Type:
- star-delta
- Standards:
- UL 508 || IEC 61812-1
- Maximum Switching Current:
- 0.333333333333333
- Reset Time:
- 120 ms on de-energisation
- Maximum Delay Response:
- 100 ms
- Overvoltage Category:
- III IEC 60664-1
- Rohs Exemption Information:
- Yes
- [Us] Rated Supply Voltage:
- 24 V DC || 24...240 V AC 50/60 Hz
- Connections - Terminals:
- screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end |
- Dielectric Strength:
- 2.5 kV 1 mA/1 minute 50 Hz between relay output and power supply basic insulation IEC 61812-1
- Relative Humidity:
- 95-95 % 25-55 °C
- Vibration Resistance:
- 20 m/s² 10-150 Hz)IEC 60068-2-6
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Setting Accuracy Of Time Delay:
- +/- 10 % of full scale 25 °C IEC 61812-1
- Voltage Drift:
- +/- 0.2 %/V
- Supply Frequency:
- 50...60 Hz +/- 5 %
- Input Voltage:
- <= 2.4 V
- Width:
- 22.5 mm
- Insulation Resistance:
- 100 MOhm 500 V DC IEC 60664-1
- Minimum Switching Current:
- 10 mA 5 V DC
- Status Led:
- Green LED backlight steady)dial pointer indication || Yellow LED steady)output relay energised || Yellow LED fast flashing)timing in progress and output relay de-energised || Yellow LED slow flashing)timing in progress and output relay energised
- Ip Degree Of Protection:
- housing IP40 IEC 60529 || front face IP50 IEC 60529 || terminals IP20 IEC 60529
- Mechanical Durability:
- 10000000 cycles
- Nominal Output Current:
- 0.333333333333333
- Sustainable Offer Status:
- Green Premium product
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Circularity Profile:
- ENVEOLI1401008EN
- Electrical Durability:
- 100000 cycles, 8 A at 250 V, AC-1 || 100000 cycles, 2 A at 24 V, DC-1
- Switching Capacity In Va:
- 2000 VA
- Tightening Torque:
- 0.6-1 N.m IEC 60947-1
- Environmental Disclosure:
- ENVPEP1401008EN
- Contacts Type And Composition:
- 1 C/O timed contact, cadmium free
- China Rohs Regulation:
- X
- Directives:
- 2004/108/EC - electromagnetic compatibility || 2006/95/EC - low voltage directive
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Temperature Drift:
- +/- 0.05 %/°C
- Electromagnetic Compatibility:
- fast transients immunity test - test level: 1 kV level 3 (capacitive connecting clip) conforming to IEC 61000-4-4 || surge immunity test - test level: 1 kV level 3 (differential mode) conforming to IEC 61000-4-5 || surge immunity test - test level: 2
- Product Or Component Type:
- single function relay
- Catalog:
- View
- Datasheet:
- View