Schneider Electric RE22R2MYMR Multifunction Timer Relay

(No reviews yet) Write a Review
SKU:
RE22R2MYMR
UPC:
3606480792533
Condition:
New
Setting Accuracy Of Time Delay:
+/- 10 % of full scale 25 °C IEC 61812-1
Supply Frequency:
50...60 Hz +/- 5 %
[Uimp] Rated Impulse Withstand Voltage:
5 kV 1.2-50 µs IEC 60664-1
Safety Reliability Data:
B10d = 160000 || MTTFd = 171.2 years
Electromagnetic Compatibility:
fast transients immunity test - test level: 1 kV level 3 (capacitive connecting clip) conforming to IEC 61000-4-4 || surge immunity test - test level: 1 kV level 3 (differential mode) conforming to IEC 61000-4-5 || surge immunity test - test level: 2
Time Delay Range:
3...30 min || 30...300 min || 0.3...3 s || 3...30 h || 10...100 s || 1...10 s || 0.05...1 s || 30...300 s || 30...300 h || 3...30 s
Shock Resistance:
15 gn not operating 11 ms IEC 60068-2-27 || 5 gn in operation 11 ms IEC 60068-2-27
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Input Voltage:
<= 2.4 V
Repeat Accuracy:
+/- 0.5 % IEC 61812-1
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Electrical Durability:
100000 cycles, 8 A at 250 V, AC-1 || 100000 cycles, 2 A at 24 V, DC-1
Mechanical Durability:
10000000 cycles
Power Consumption In W:
1.5 W 240 V DC
Voltage Drift:
+/- 0.2 %/V
Environmental Disclosure:
ENVPEP1401008EN
Sustainable Offer Status:
Green Premium product
Product Or Component Type:
multifunction relay
Overvoltage Category:
III IEC 60664-1
Range Of Product:
Harmony Timer Relays
Rohs Exemption Information:
Yes
Dielectric Strength:
2.5 kV 1 mA/1 minute 50 Hz between relay output and power supply basic insulation IEC 61812-1
Net Weight:
0.105 kg
Switching Capacity In Va:
2000 VA
Immunity To Microbreaks:
10 ms
Control Type:
rotary knob || diagnostic button || potentiometer external
Voltage Range:
0.85...1.1 Us
Housing Material:
self-extinguishing
Standards:
UL 508 || IEC 61812-1
Reset Time:
120 ms on de-energisation
Product Certifications:
RCM || CE || EAC || CSA || CCC || UL || GL
Device Short Name:
RE22
Insulation Resistance:
100 MOhm 500 V DC IEC 60664-1
Discrete Output Type:
relay
Tightening Torque:
0.6-1 N.m IEC 60947-1
Mercury Free:
Yes
Contacts Type And Composition:
1 C/O timed or instantaneous contact, cadmium free || 2 C/O timed contact, cadmium free
Ambient Air Temperature For Operation:
-20-60 °C
Status Led:
Green LED backlight steady)dial pointer indication || Yellow LED steady)output relay energised || Yellow LED fast flashing)timing in progress and output relay de-energised || Yellow LED slow flashing)timing in progress and output relay energised
Vibration Resistance:
20 m/s² 10-150 Hz)IEC 60068-2-6
[Us] Rated Supply Voltage:
24...240 V AC/DC 50/60 Hz
Connections - Terminals:
screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end || s
Mounting Position:
any position
Nominal Output Current:
0.333333333333333
Width:
22.5 mm
Temperature Drift:
+/- 0.05 %/°C
China Rohs Regulation:
X
Ip Degree Of Protection:
housing IP40 IEC 60529 || terminals IP20 IEC 60529 || front panel IP50 IEC 60529
Minimum Pulse Duration:
100 ms with load in parallel || 30 ms
Relative Humidity:
95-95 % 25-55 °C
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Maximum Delay Response:
100 ms
Function Available:
A- Power on-delay relay-2 C/O || At- Power on-delay relay w/ pause/summation (X1)-2 C/O || Aw- Power on-delay relay w/ retrigger/restart-2 C/O || C- Off-delay relay w/ control signal-2 C/O || Ct- Off-delay relay w/ control signal and pause/summation-
Circularity Profile:
ENVEOLI1401008EN
Maximum Switching Voltage:
250 V AC
Mounting Support:
35 mm DIN rail conforming to IEC 60715
Creepage Distance:
4 kV/3 IEC 60664-1
Pollution Degree:
3 IEC 60664-1
Maximum Switching Current:
0.333333333333333
Minimum Switching Current:
10 mA 5 V DC
Time Delay Type:
power on-delay || off-delay || symmetrical flashing || interval || star-delta
Directives:
2004/108/EC - electromagnetic compatibility || 2006/95/EC - low voltage directive
Power Consumption In Va:
3-3 VA 240 V AC
Ambient Air Temperature For Storage:
-40-70 °C
  • Schneider Electric RE22R2MYMR Multifunction Timer Relay
  • Schneider Electric RE22R2MYMR Multifunction Timer Relay
  • Schneider Electric RE22R2MYMR Multifunction Timer Relay
$79.16

Description

This Harmony RE22 timing relay can be set between 0.05 seconds and 300 hours, has an output rating of 8A, is 22.5mm wide and can be supplied with 24V to 240V AC. It has one of market slimmest form-factors, allowing for a flexible and easy installation on DIN rail. It also offers a sealable cover, simple and precise settings with rotary trimmers. multi function timer for a simple integration in hard-wired logic schematics, ideal for refurbishment of old installations without using a PLC. Status display with 2 LEDs, visually inspect the status of you system without specialized tools. Diagnostic button allows simple setup and trouble shooting by non-specialists. 0 0 0 0 0 0 0 0 0 0 0 0 0
View AllClose