- Wire Stripping Length:
- 35 mm
- Trip Unit Name:
- MicroLogic 6.0 A
- Electrical Connection:
- busbar connection, line || busbar connection, load
- Height:
- 16.24 in
- Mercury Free:
- Yes
- Mounting Mode:
- unit mount busbar)
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Net Weight:
- 52 lb(US)
- Sustainable Offer Status:
- Green Premium product
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Network Frequency:
- 50/60 Hz
- Product Name:
- PowerPact R
- Device Application:
- distribution
- Quality Labels:
- CE
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Eu Rohs Directive:
- Compliant with Exemptions
- Rohs Exemption Information:
- Yes
- Terminal Identifier:
- AL2500RK
- Ambient Air Temperature For Operation:
- -25-70 °C
- Environmental Disclosure:
- ENVPEP2206034EN
- Circularity Profile:
- ENVEOLI2206034EN
- Pollution Degree:
- 3 IEC 60947-1
- Poles Description:
- 3P
- Quantity Per Set:
- 1
- Tightening Torque:
- 68-68 N.m 50-400 mm² (AWG 1/0...750 kcmil) || 68-68 N.m 50-150 mm² (2 x AWG 1/0...2 x 300 kcmil)
- Awg Gauge:
- AWG 3/0...750 kcmil aluminium/copper
- Standards:
- UL || CSA || NEMA || NMX J-266 || IEC 60947-2
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Depth:
- 14.49 in
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 6.0 A, LSIG
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Local Signalling:
- alarm 1 LED yellow)long-time pick up) || 1 LED red)long-time pick up) || trip causes 1 LED red) || 1 LED red)digital ammeter) || ground indicator 1 LED red) || phase-loading LED green)load balancing)
- Width:
- 16.53 in
- Continuous Current Rating:
- 0.8
- Circuit Breaker Application:
- HACR rated
- Breaking Capacity Code:
- G
- Halogen Content Performance:
- Halogen free plastic parts product
- Line Rated Current:
- 2000-2000 A
- Range:
- PowerPact
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Pvc Free:
- Yes
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Suitability For Isolation:
- yes IEC 60947-2
- Ip Degree Of Protection:
- IP40
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Product Certifications:
- UL || CSA || NOM
- Utilisation Category:
- category A
- Warranty:
- 18 months
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Product Or Component Type:
- circuit breaker
- Ambient Air Temperature For Storage:
- -50-85 °C
- Mounting Support:
- busbar
- Control Type:
- operating handle
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2