- Pvc Free:
- Yes
- Pollution Degree:
- 3 IEC 60947-1
- Ip Degree Of Protection:
- IP40
- Width:
- 16.53 in
- Ambient Air Temperature For Storage:
- -50-85 °C
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Depth:
- 14.49 in
- Range:
- PowerPact
- Net Weight:
- 52 lb(US)
- Magnetic Tripping Current:
- 1800-14400 A
- Product Name:
- PowerPact R
- Halogen Content Performance:
- Halogen free plastic parts product
- Continuous Current Rating:
- 0.8
- Utilisation Category:
- category A
- Ambient Air Temperature For Operation:
- -25-70 °C
- Awg Gauge:
- AWG 3/0...750 kcmil aluminium/copper
- Electrical Connection:
- busbar connection, line || busbar connection, load
- Circuit Breaker Application:
- HACR rated
- Warranty:
- 18 months
- Product Certifications:
- UL || CSA || NOM
- Line Rated Current:
- 1200-1200 A
- Height:
- 16.24 in
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Mercury Free:
- Yes
- Quality Labels:
- CE
- Sustainable Offer Status:
- Green Premium product
- Network Frequency:
- 50/60 Hz
- Wire Stripping Length:
- 35 mm
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Environmental Disclosure:
- ENVPEP2206034EN
- Tightening Torque:
- 68-68 N.m 50-400 mm² (AWG 1/0...750 kcmil) || 68-68 N.m 50-150 mm² (2 x AWG 1/0...2 x 300 kcmil)
- Poles Description:
- 3P
- Control Type:
- operating handle
- Circularity Profile:
- ENVEOLI2206034EN
- Rohs Exemption Information:
- Yes
- Breaking Capacity Code:
- J
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Mounting Support:
- busbar
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Suitability For Isolation:
- yes IEC 60947-2
- Device Application:
- distribution
- Eu Rohs Directive:
- Compliant with Exemptions
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Local Signalling:
- trip indicator
- Standards:
- UL || CSA || NEMA || NMX J-266 || IEC 60947-2
- Quantity Per Set:
- 1
- Trip Unit Name:
- ET 1.0I
- Terminal Identifier:
- AL2500RK
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Product Or Component Type:
- circuit breaker
- Trip Unit Technology:
- electronic, basic, ET 1.0I, I
- Mounting Mode:
- unit mount busbar)