- Tightening Torque:
- 68-68 N.m 50-400 mm² (AWG 1/0...750 kcmil) || 68-68 N.m 50-150 mm² (2 x AWG 1/0...2 x 300 kcmil)
- Warranty:
- 18 months
- Ambient Air Temperature For Storage:
- -50-85 °C
- Line Rated Current:
- 1600-1600 A
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Quantity Per Set:
- 1
- Rohs Exemption Information:
- Yes
- Pollution Degree:
- 3 IEC 60947-1
- Network Frequency:
- 50/60 Hz
- Breaking Capacity Code:
- J
- Mounting Support:
- busbar
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Standards:
- UL || CSA || NEMA || NMX J-266 || IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Product Name:
- PowerPact R
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Ip Degree Of Protection:
- IP40
- Terminal Identifier:
- AL2500RK
- Width:
- 16.53 in
- Height:
- 16.24 in
- Mounting Mode:
- unit mount busbar)
- Mercury Free:
- Yes
- Ambient Air Temperature For Operation:
- -25-70 °C
- Product Or Component Type:
- circuit breaker
- Sustainable Offer Status:
- Green Premium product
- Net Weight:
- 52 lb(US)
- Local Signalling:
- trip indicator
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Control Type:
- operating handle
- Continuous Current Rating:
- 0.8
- Wire Stripping Length:
- 35 mm
- Awg Gauge:
- AWG 3/0...750 kcmil aluminium/copper
- Product Certifications:
- UL || CSA || NOM
- Electrical Connection:
- busbar connection, line || busbar connection, load
- Trip Unit Name:
- ET 1.0I
- Utilisation Category:
- category A
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Device Application:
- distribution
- Suitability For Isolation:
- yes IEC 60947-2
- Range:
- PowerPact
- Environmental Disclosure:
- ENVPEP2206034EN
- Halogen Content Performance:
- Halogen free plastic parts product
- Poles Description:
- 3P
- Pvc Free:
- Yes
- Quality Labels:
- CE
- Eu Rohs Directive:
- Compliant with Exemptions
- Depth:
- 14.49 in
- Trip Unit Technology:
- electronic, basic, ET 1.0I, I
- Magnetic Tripping Current:
- 2400-19200 A
- Circularity Profile:
- ENVEOLI2206034EN
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489