Schneider Electric RM35JA31MW Oc Or Uc Relay 2..500Ma 24-240Vac/Dc

(No reviews yet) Write a Review
SKU:
RM35JA31MW
UPC:
3389119405218
Condition:
New
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Maximum Measuring Cycle:
30 ms measurement cycle as true rms value
Product Certifications:
GL || CSA || GOST || UL || C-tick
Control Circuit Frequency:
40...70 Hz +/- 10 %
Electromagnetic Compatibility:
emission standard for industrial environments conforming to IEC 61000-6-4 || emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 || immunity for industrial environments conforming to NF EN/IEC 6
Shock Resistance:
15 gn 11 ms IEC 60255-21-1
Non-Dissipating Shock Wave:
4 kV IEC 60255-5 || 4 kV IEC 60664-1 || 4 kV IEC 61000-4-5
Measurement Error:
0.05 %/°C with temperature variation || 1 by volt over the whole range with voltage variation
Polarity:
no DC
Rohs Exemption Information:
Yes
Tightening Torque:
0.6-1 N.m IEC 60947-1
Environmental Disclosure:
ENVPEP1504008EN
Control Type:
without test button
Immunity To Microbreaks:
50 ms
Range Of Product:
Harmony Control Relays
Mounting Support:
35 mm symmetrical DIN rail conforming to IEC 60715
Vibration Resistance:
0.35 mm 5-57.6 Hz)IEC 60068-2-6 || 1 gn 57.6-150 Hz)IEC 60255-21-1
[Ui] Rated Insulation Voltage:
250 V IEC 60664-1
Operating Rate:
<= 360 operations/hour full load
Connections - Terminals:
screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end ||
Switching Capacity In Va:
1250 VA
Local Signalling:
for power ON LED (green) || for relay ON LED (yellow)
Ambient Air Temperature For Operation:
-20-50 °C
Relay Type:
current control relay
Output Contacts:
2 C/O
Mechanical Durability:
30000000 cycles
Net Weight:
0.13 kg
Operating Position:
any position without derating
Resistance Across Terminals:
1 Ohm E2-M terminals || 5 Ohm E1-M terminals || 0.2 Ohm E3-M terminals
Threshold Setting:
10...100 %
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Maximum Switching Current:
5 A AC
Warranty:
18 months
Utilisation Category:
AC-12 IEC 60947-5-1 || AC-13 IEC 60947-5-1 || AC-14 IEC 60947-5-1 || AC-15 IEC 60947-5-1 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1 || DC-14 IEC 60947-5-1
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Time Delay Type:
adjustable 0.3...30 s, 0 + 10 % Tt- time delay upon fault || adjustable 1...20 s, 0 + 10 % Ti- inhibition time delay upon startup
Standards:
IEC 60255-6
Circularity Profile:
ENVEOLI1504008EN
Minimum Switching Current:
10 mA 5 V DC
Marking:
CE : EMC 89/336/EEC || CE : 73/23/EEC
Relay Monitored Parameters:
overcurrent or undercurrent in window mode || overcurrent or undercurrent detection
Repeat Accuracy:
+/- 0.5 % input and measurement circuit || +/- 2 % time delay
Product Or Component Type:
current control relay
Safety Reliability Data:
MTTFd = 296.8 years || B10d = 270000
Dielectric Test Voltage:
2 kV AC 50 Hz, 1 min IEC 60255-5 || 2 kV AC 50 Hz, 1 min IEC 60664-1
Measurement Range:
2...500 mA AC/DC E2-M terminals || 2...20 mA E1-M terminals || 2...500 mA current || 50...500 mA E3-M terminals
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Electrical Durability:
100000 cycles
Maximum Power Consumption In Va:
3.5 VA AC
Ambient Air Temperature For Storage:
-40-70 °C
Supply Voltage Limits:
20.4-264 V AC/DC
Sustainable Offer Status:
Green Premium product
Maximum Power Consumption In W:
0.6 W DC
Mercury Free:
Yes
Relative Humidity:
95-95 % 55-55 °C IEC 60068-2-30
[Us] Rated Supply Voltage:
AC/DC non self-powered
Hysteresis:
5-50 % threshold setting
Overvoltage Category:
III IEC 60664-1
Measurement Accuracy:
+/- 10 % of the full scale value
Relay Name:
RM35JA
Insulation Resistance:
> 500 MOhm 500 V DC between supply and relay output IEC 60255-5 || > 500 MOhm 500 V DC between measurement and relay output IEC 60664-1 || > 1 MOhm 500 V DC between supply and measurement IEC 60255-5 || > 500 MOhm 500 V DC between supply and relay ou
Ip Degree Of Protection:
IP20 IEC 60529 terminals) || IP30 IEC 60529 casing)
Width:
35 mm
Reset Time:
1500 ms time delay
Nominal Output Current:
0.208333333333333
Run-Up Delay At Power-Up:
0.3 s
Housing Material:
self-extinguishing plastic
Contacts Type And Composition:
2 C/O
Pollution Degree:
3 IEC 60664-1
Maximum Switching Voltage:
250 V AC
China Rohs Regulation:
X
Control Circuit Voltage Limits:
15 % + 10 % Un
Contacts Material:
cadmium free
Catalog:
View
Datasheet:
View
  • Schneider Electric RM35JA31MW Oc Or Uc Relay 2..500Ma 24-240Vac/Dc
  • Schneider Electric RM35JA31MW Oc Or Uc Relay 2..500Ma 24-240Vac/Dc
  • Schneider Electric RM35JA31MW Oc Or Uc Relay 2..500Ma 24-240Vac/Dc
$148.00

Description

This Harmony RM35-JA relay allows monitoring of current control in single phase networks. This modular multi function single phase current control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market medium form-factors with 35mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 3-pole DIN device. It also offers a sealable cover, simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0
View AllClose