Schneider Electric RM35UA13MW Ov Or Uv Relay 15..600V 24-240Vac/Dc 2Co
Schneider Electric
$157.00
This Harmony RM35-U multi function control relay allows monitoring of voltage control. This modular multi function control relay is ideal for monitoring of electrical values and voltage variation in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market medium form-factors with 35mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 3-pole DIN device. It also offers a selectable memory function, integral LED for indicating control status, sealable cover, with simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. Multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0
- Maximum Power Consumption In W:
- 0.6 W DC
- Directives:
- 73/23/EEC - low voltage directive || 89/336/EEC - electromagnetic compatibility
- Contacts Type And Composition:
- 2 C/O
- Supply Voltage Limits:
- 20.4-264 V AC/DC
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Tightening Torque:
- 0.6-1 N.m IEC 60947-1
- Operating Rate:
- <= 360 operations/hour full load
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Relay Name:
- RM35UA
- Electrical Durability:
- 100000 cycles
- Relative Humidity:
- 95-95 % 55-55 °C IEC 60068-2-30
- China Rohs Regulation:
- X
- Control Circuit Voltage Limits:
- 15 % + 10 % Un
- Product Certifications:
- GOST || UL || GL || C-tick || CSA
- Utilisation Category:
- AC-12 IEC 60947-5-1 || AC-13 IEC 60947-5-1 || AC-14 IEC 60947-5-1 || AC-15 IEC 60947-5-1 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1 || DC-14 IEC 60947-5-1
- Output Contacts:
- 2 C/O
- Shock Resistance:
- 5 gn IEC 60068-2-27
- Sustainable Offer Status:
- Green Premium product
- Warranty:
- 18 months
- Threshold Setting:
- 10...100 %
- Product Or Component Type:
- voltage control relay
- Sensitivity Scale:
- 15...150 V E1-M terminals || 30...300 V E2-M terminals || 60...600 V E3-M terminals
- Minimum Switching Current:
- 10 mA 5 V DC
- Mounting Support:
- 35 mm symmetrical DIN rail conforming to IEC 60715
- Overvoltage Category:
- III IEC 60664-1
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Mercury Free:
- Yes
- Range Of Product:
- Harmony Control Relays
- Ip Degree Of Protection:
- IP20 IEC 60529 terminals) || IP30 IEC 60529 casing)
- Connections - Terminals:
- screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...2 x 2.5 mm² AWG 24...AWG 12) flexible with cable end ||
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- [Ui] Rated Insulation Voltage:
- 250 V IEC 60664-1 || 600 V IEC 60664-1
- Hysteresis:
- 5-50 % threshold setting
- Ambient Air Temperature For Storage:
- -40-70 °C
- Insulation Resistance:
- > 500 MOhm 500 V DC between supply and relay output IEC 60255-5 || > 500 MOhm 500 V DC between measurement and relay output IEC 60664-1 || > 1 MOhm 500 V DC between supply and measurement IEC 60255-5 || > 500 MOhm 500 V DC between supply and relay ou
- Maximum Measuring Cycle:
- 30 ms measurement cycle as true rms value
- Relay Monitored Parameters:
- overvoltage or undervoltage detection
- Resistance Across Terminals:
- 150 mOhm E1-M terminals || 300 mOhm E2-M terminals || 600 mOhm E3-M terminals
- Reset Time:
- 1500 ms time delay
- Compatibility Code:
- RM3
- Nominal Output Current:
- 0.208333333333333
- Mechanical Durability:
- 30000000 cycles
- Control Circuit Frequency:
- 40...70 Hz +/- 10 %
- Maximum Switching Current:
- 5 A AC/DC
- Measurement Error:
- +/- 0.05 %/°C with temperature variation || < 1 % over the whole range with voltage variation
- Repeat Accuracy:
- +/- 0.5 % input and measurement circuit || +/- 2 % time delay
- Polarity:
- non reversible polarity on DC supply
- Switching Capacity In Va:
- 1250 VA
- Net Weight:
- 0.08 kg
- Rohs Exemption Information:
- Yes
- Standards:
- IEC 60255-6
- Power Consumption In Va:
- 0-3.5 VA AC
- Relay Type:
- multifunction voltage control relay
- Measurement Accuracy:
- +/- 10 % of the full scale value
- Run-Up Delay At Power-Up:
- 600 ms
- Non-Dissipating Shock Wave:
- 4 kV IEC 60255-5 || 4 kV IEC 60664-1 || 4 kV IEC 61000-4-5
- [Us] Rated Supply Voltage:
- AC/DC non self-powered
- Maximum Switching Voltage:
- 250 V AC/DC
- Housing Material:
- self-extinguishing plastic
- Immunity To Microbreaks:
- 10 ms
- Time Delay Type:
- adjustable 0.3...30 s, 0 + 10 % Tt- time delay upon fault
- Circularity Profile:
- ENVEOLI1504008EN
- Environmental Disclosure:
- ENVPEP1504008EN
- Electromagnetic Compatibility:
- emission standard for industrial environments conforming to IEC 61000-6-4 || emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 || immunity for industrial environments conforming to NF EN/IEC 6
- Measurement Range:
- 15...600 V voltage AC/DC
- Control Type:
- without test button
- Width:
- 35 mm
- Dielectric Test Voltage:
- 2 kV AC 50 Hz, 1 min IEC 60255-5 || 2 kV AC 50 Hz, 1 min IEC 60664-1
- Safety Reliability Data:
- B10d = 290000 || MTTFd = 308.2 years
- Ambient Air Temperature For Operation:
- -20-50 °C
- Quality Labels:
- CE
- Local Signalling:
- for power ON LED (green) || for relay ON LED (yellow)
- Operating Position:
- any position without derating
- Vibration Resistance:
- 0.35 mm 5-57.6 Hz)IEC 60068-2-6 || 1 gn 57.6-150 Hz)IEC 60255-21-1
- Pollution Degree:
- 3 IEC 60664-1
- Catalog:
- View
- Datasheet: