Schneider Electric RUMC31ND 3Co 10A Relay Cylind +Ltb-Led 60Vdc
Schneider Electric
$13.79
This Harmony RUM universal plug-in relay uses cylindrical pins, has a control coil voltage of 60V DC and has 3 changeover contacts triple pole double throw with a rating of 10A." "It provides a complete system solution for the most demanding applications." "It also offers one-step lockable test button." "It helps to reduce the size of enclosures and increase machine reliability, you can mount nearly everywhere." "The product is IP40 and has a transparent cover allowing operator to visually inspect the status of contacts." "Workability for hard-wired logic automated systems to complement the functions of industrial programmable logic controllers (PLCs)." 0 0 0 0 0 0 0 0 0 0
- Ip Degree Of Protection:
- IP40
- Net Weight:
- 0.086 kg
- Range Of Product:
- Harmony Electromechanical Relays
- Status Led:
- without
- Rohs Exemption Information:
- Yes
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other repr
- Environmental Disclosure:
- ENVPEP1406038EN
- Ambient Air Temperature For Storage:
- -40-85 °C
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- [Ie] Rated Operational Current:
- 10 A at 277 V AC conforming to UL || 10 A at 30 V DC conforming to UL || 10 A at 277 V AC (same polarity) conforming to CSA || 10 A at 30 V DC conforming to CSA || 5 A at 250 V AC (NC) conforming to IEC || 5 A at 28 V DC (NC) conforming to IEC || 10
- China Rohs Regulation:
- X
- [Ithe] Conventional Enclosed Thermal Current:
- 10 A -40-55 °C
- Test Levels:
- level A group mounting
- Contacts Material:
- AgNi
- Utilisation Coefficient:
- 0.2
- Load Current:
- 10 A 250 V AC || 10 A 28 V DC
- Circularity Profile:
- N/A
- Ambient Air Temperature For Operation:
- -40-55 °C
- Operating Rate:
- <= 18000 cycles/hour no-load || <= 1200 cycles/hour under load
- Drop-Out Voltage Threshold:
- >= 0.1 Uc DC
- Reach Free Of Svhc:
- Yes
- Device Presentation:
- complete product
- Dielectric Strength:
- 1500 V AC between contacts with micro disconnection || 2500 V AC between coil and contact with reinforced || 2000 V AC between poles with basic
- Product Certifications:
- CSA || UL || EAC
- Mechanical Durability:
- 5000000 cycles
- Standards:
- UL 508 || CSA C22.2 No 14 || IEC 61810-1
- Maximum Switching Capacity:
- 2500 VA/280 W
- Operating Position:
- any position
- Average Resistance:
- 2790 Ohm 20 °C +/- 15 %
- [Ui] Rated Insulation Voltage:
- 250 V IEC || 300 V CSA || 300 V UL
- Protection Category:
- RT I
- Safety Reliability Data:
- B10d = 100000
- Series Name:
- Universal
- Average Coil Consumption:
- 1.4 W
- Shape Of Pin:
- cylindrical
- Reset Time:
- 20 ms at nominal voltage
- [Uc] Control Circuit Voltage:
- 60 V DC
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Minimum Switching Capacity:
- 170 mW 10 mA, 17 V
- Product Or Component Type:
- plug-in relay
- Sustainable Offer Status:
- Green Premium product
- Electrical Durability:
- 100000 cycles resistive
- Pollution Degree:
- 2
- Vibration Resistance:
- 3 gn +/- 1 mm 10-150 Hz)5 cycles in operation || 4 gn +/- 1 mm 10-150 Hz)5 cycles not operating
- Operating Time:
- 20 ms at nominal voltage
- Rated Operational Voltage Limits:
- 48...66 V DC
- Maximum Switching Voltage:
- 250 V IEC
- Contacts Type And Composition:
- 3 C/O
- [Uimp] Rated Impulse Withstand Voltage:
- 4 kV 1.2/50 µs)
- Control Type:
- lockable test button
- Shock Resistance:
- 10 gn 11 ms) in operation IEC 60068-2-27 || 10 gn 11 ms) not operating IEC 60068-2-27
- Device Short Name:
- RUM
- Catalog:
- View
- Datasheet:
- View