Schneider Electric TM221ME16T Controller M221-16Io Tr.Pnp Eth Modular
Schneider Electric
$386.25
This product is part of the Modicon M221 range, an offer of programmable logic controllers for hardwired architectures. This logic controller provides 8 discrete, 4 fast inputs, 8 transistor, 2 fast outputs with ethernet PNP transistor output with 10bit resolution. It is a Modicon logic controller with a rated supply/output voltage of 24V DC, an output current of 0.5A with sink or source input logic and positive output logic. This product requires minimal installation and offers tremendous versatility. Integrated connections are USB port with mini B USB 2.0 connector, non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface and ethernet with RJ45 connector. It is a Modicon M221 controller with 256kB for user application and data RAM, internal variables RAM, 256kB built-in flash memory and a SD card memory capacity of 2GB. It is an IP20 rated product. Its dimensions are 70mm (Width) x 70mm (Depth) x 90mm (Height). It weighs 0.264kg. This product is certified by CE, IACS E10, CSA, RCM, LR, ABS, DNV-GL, EAC and CULus. It meets EN/IEC 61010-2-201, EN/IEC 61131-2 and EN/IEC 60664-1 standards. It supports DIN rail mount. Achieve benchmark performance while increasing profitability with the Modicon M221 through intuitive machine programming with SoMachine Basic, ready-to-use applications and function blocks
- Product Certifications:
- RCM || ABS || cULus || DNV-GL || EAC || LR || CE || UKCA || cULus HazLoc
- Regulation Loop:
- adjustable PID regulator up to 14 simultaneous loops
- Width:
- 70 mm
- Sustainable Offer Status:
- Green Premium product
- Electrical Connection:
- terminal block, 3 for connecting the 24 V DC power supply || connector, 4 for analogue inputs || mini B USB 2.0 connector for a programming terminal || removable screw terminal block, 10 for inputs || removable screw terminal block, 11 for outputs
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Surge Withstand:
- 2 kV power lines (AC) common mode IEC 61000-4-5 || 2 kV relay output common mode IEC 61000-4-5 || 1 kV I/O common mode IEC 61000-4-5 || 1 kV shielded cable common mode IEC 61000-4-5 || 0.5 kV power lines (DC) differential mode IEC 61000-4-5 || 1 kV p
- Ip Degree Of Protection:
- IP20 with protective cover in place
- Pollution Degree:
- <= 2
- Backup Time:
- 1 year 25 °C by interruption of power supply)
- Discrete Input Number:
- 8 , discrete input 4 fast input IEC 61131-2 Type 1
- Voltage State 0 Guaranteed:
- <= 5 V input
- Configurable Filtering Time:
- 0 ms input || 3 ms input || 12 ms input
- Operating Altitude:
- 0...6561.68 ft (0...2000 m)
- Height:
- 90 mm
- Power Supply Output Current:
- 0.52-0.52 A 5 V expansion bus || 0.49-0.49 A 24 V expansion bus
- Resistance To Fast Transients:
- 2 kV IEC 61000-4-4 power lines) || 2 kV IEC 61000-4-4 relay output) || 1 kV IEC 61000-4-4 I/O) || 1 kV IEC 61000-4-4 Ethernet line) || 1 kV IEC 61000-4-4 serial link)
- Resistance To Electrostatic Discharge:
- 8 kV in air IEC 61000-4-2 || 4 kV on contact IEC 61000-4-2
- Discrete Output Logic:
- positive logic (source)
- Discrete Input Voltage Type:
- DC
- Environmental Disclosure:
- ENVPEP1403012EN
- Supply:
- serial 1)serial link supply 5 V, <200 mA
- Maximum Current Per Output Common:
- 0.166666666666667
- Absolute Accuracy Error:
- +/- 1 % of full scale analog input
- Marking:
- CE
- Immunity To Microbreaks:
- 10 ms
- Application Structure:
- 1 cyclic auxiliary task || 1 configurable freewheeling/cyclic master task || 8 interrupt tasks
- Discrete Output Number:
- 8 transistor 2 fast output
- Depth:
- 70 mm
- Communication Port Protocol:
- USB port USB - SoMachine-Network || non isolated serial link Modbus master/slave - RTU/ASCII or SoMachine-Network || Ethernet
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Permitted Overload On Inputs:
- +/- 30 V DC 5 min maximum)analog input || +/- 13 V DC permanent)analog input
- Maximum Power Consumption In W:
- 22.9 W 24 V with max number of I/O expansion module) || 4 W 24 V without I/O expansion module)
- Battery Type:
- BR2032 or CR2032X lithium non-rechargeable
- Rohs Exemption Information:
- Yes
- Standards:
- IEC 61131-2 || UL 508 || CAN/CSA C22.2 No. 213 || IACS E10 || ANSI/ISA 12-12-01
- Maximum Tungsten Load:
- <12 W output and fast output
- Data Backed Up:
- 256 kB built-in flash memory backup of application and data
- Maximum Voltage Drop:
- <1 V
- Mechanical Durability:
- 20000000 cycles transistor output
- Vibration Resistance:
- 3.5 mm 5-8.4 Hz symmetrical rail || 3.5 mm 5-8.4 Hz panel mounting || 1 gn 8.4-150 Hz symmetrical rail || 1 gn 8.4-150 Hz panel mounting
- Discrete Input Current:
- 7 mA discrete input || 5 mA fast input
- Memory Capacity:
- 256 kB user application and data RAM 10000 instructions || 256 kB internal variables RAM
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Resistance To Magnetic Fields:
- 30 A/m 50/60 Hz IEC 61000-4-8
- Resistance To Electromagnetic Fields:
- 10 V/m 80 MHz...1 GHz IEC 61000-4-3 || 3 V/m 1.4 GHz...2 GHz IEC 61000-4-3 || 1 V/m 2...2.7 GHz IEC 61000-4-3
- Resistance To Conducted Disturbances:
- 10 V 0.15...80 MHz IEC 61000-4-6 || 3 V 0.1...80 MHz Marine specification (LR, ABS, DNV, GL) || 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) Marine specification (LR, ABS, DNV, GL)
- Execution Time For 1 Kinstruction:
- 0.3 ms event and periodic task || 0.7 ms other instruction
- Exct Time For Event Task:
- 60 µs response time
- Insulation:
- between input and internal logic 500 V AC || between fast input and internal logic 500 V AC || non-insulated between inputs || between output and internal logic 500 V AC || non-insulated between analogue input and internal logic || non-insulated betw
- Relative Humidity:
- 10-95 %, without condensation in operation) || 10-95 %, without condensation in storage)
- Discrete Output Current:
- 0.5 A
- Counting Input Number:
- 4 fast input (HSC mode) 100 kHz 32 bits
- Inrush Current:
- 35 A
- Electromagnetic Emission:
- conducted emissions 79 dBμV/m QP/66 dBμV/m AV power lines (AC))0.15-0.5 MHz IEC 55011 || conducted emissions 73 dBμV/m QP/60 dBμV/m AV power lines (AC))0.5-300 MHz IEC 55011 || conducted emissions 120...69 dBµV/m QP power lines)10-150 kHz IEC 55
- Response Time:
- 35 µs turn-off, I2...I5 input || 5 µs turn-on, I0, I1, I6, I7 fast input || 35 µs turn-on, other terminals input || 5 µs turn-off, I0, I1, I6, I7 fast input || 100 µs turn-off, other terminals input || 5 µs turn-on, turn-off, Q0...Q1 output ||
- Realtime Clock:
- with
- Control Signal Type:
- pulse/direction || A/B || single phase
- Input Impedance:
- 100 kOhm analog input || 3.4 kOhm input || 4.9 kOhm fast input
- Mercury Free:
- Yes
- Reset Time:
- 1 s automatic reset
- Clock Drift:
- <= 30 s/month 25-25 °C
- Port Ethernet:
- 10BASE-T/100BASE-TX 1 100 m copper cable
- Discrete Input Logic:
- sink or source (positive/negative)
- Analogue Input Resolution:
- 10 bits
- Voltage State 1 Guaranteed:
- >= 15 V input
- Product Or Component Type:
- logic controller
- [Us] Rated Supply Voltage:
- 24 V DC
- Lsb Value:
- 10 mV
- Net Weight:
- 0.264 kg
- Environmental Characteristic:
- ordinary and hazardous location
- Integrated Connection Type:
- USB port mini B USB 2.0 || non isolated serial link serial 1 RJ45 RS232/RS485 || Ethernet RJ45
- Function Available:
- PLS || frequency generator || PWM
- Output Frequency:
- 100 kHz fast output (PWM/PLS mode) Q0...Q1 || 5 kHz output Q2...Q3 || 0.1 kHz output Q4...Q6
- Protection Type:
- short-circuit and overload protection with automatic reset || short-circuit protection on output || overload and short-circuit protection 1 A
- Pvc Free:
- Yes
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Communication Service:
- DHCP client || Ethernet/IP adapter || Modbus TCP server || Modbus TCP slave device || Modbus TCP client
- Ambient Air Temperature For Storage:
- -25-70 °C
- Data Storage Equipment:
- 2 GB SD card optional)
- Mounting Support:
- top hat type TH35-15 rail IEC 60715 || top hat type TH35-7.5 rail IEC 60715 || plate or panel with fixing kit
- Maximum Number Of I/O Expansion Module:
- 7 (local I/O-Architecture) || 14 (remote I/O-Architecture)
- Storage Altitude:
- 0-3000 m
- Ambient Air Temperature For Operation:
- -10-55 °C horizontal installation) || -10-35 °C vertical installation)
- Transmission Rate:
- 1.2...115.2 kbit/s (115.2 kbit/s by default) 15-15 m RS485 || 1.2...115.2 kbit/s (115.2 kbit/s by default) 3-3 m RS232 || 480 Mbit/s USB
- Range Of Product:
- Modicon M221
- Circularity Profile:
- ENVEOLI1403012EN
- Discrete Input Voltage:
- 24 V
- Analogue Input Number:
- 2 0...10 V
- Supply Voltage Limits:
- 20.4-28.8 V
- Discrete I/O Number:
- 16
- Maximum Leakage Current:
- 0.1 mA transistor output
- Execution Time Per Instruction:
- 0.2 µs Boolean
- Shock Resistance:
- 147 m/s² 11 ms
- Maximum Size Of Object Areas:
- 512 %M memory bits || 512 %KW constant words || 8000 %MW memory words || 255 %TM timers || 255 %C counters
- China Rohs Regulation:
- X
- Maximum Cable Distance Between Devices:
- shielded cable <10 m fast input || unshielded cable <30 m output || unshielded cable <30 m digital input || unshielded cable <1 m analog input || shielded cable <3 m fast output
- Discrete Output Type:
- transistor
- Conversion Time:
- 1 ms per channel + 1 controller cycle time analog input
- Positioning Functions:
- PTO 2 pulse/direction 100 kHz) || PTO 1 CW/CCW 100 kHz)
- Discrete Output Voltage:
- 24 V DC
- Local Signalling:
- for PWR 1 LED (green) || for RUN 1 LED (green) || for module error (ERR) 1 LED (red) || for SD card access (SD) 1 LED (green) || for BAT 1 LED (red) || for I/O state 1 LED per channel (green) || for SL 1 LED (green) || for ACT Ethernet network activi
- Catalog:
- View
- Datasheet:
- View