Schneider Electric XB6AS8349B Red Emergency S To P Diam 16 Mushroom He
Schneider Electric
$73.40
$1200 Minimum Order for Non-stock Items or $60 Addl Schneider Handling Fee Applies
This Harmony XB6 red, complete emergency stop push button is part of the range diameter 16mm plastic, Harmony XB6 modular. It has a circular head shape, with a turn to release mushroom, diameter 30mm, with trigger action and mechanical latching. It features 1 NO + 2 NC slow break contacts and faston connection type. Its reduced diameter 16mm makes it suitable to applications where less space is available for mounting, like small machines and control panels. It is impact resistant, dust resistant, water resistant and vibration resistant thanks to its IP65.
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Positive Opening:
- with IEC 60947-5-1 appendix K
- Electrical Durability:
- 1000000 cycles, AC-15 230 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C || 1000000 cycles, DC-13 230 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C
- Bezel Material:
- plastic
- Shock Resistance:
- 30 gn 18 ms) half sine wave acceleration IEC 60068-2-27 || 50 gn 11 ms) half sine wave acceleration IEC 60068-2-27
- Nema Degree Of Protection:
- NEMA 13 UL 50 || NEMA 4 UL 50 || NEMA 4X UL 50 || NEMA 13 CSA C22.2 No 94 || NEMA 4X CSA C22.2 No 94 || NEMA 4 CSA C22.2 No 94
- Reach Free Of Svhc:
- Yes
- Mechanical Durability:
- 100000 cycles
- [Uimp] Rated Impulse Withstand Voltage:
- 4 kV IEC 60947-1
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Toxic Heavy Metal Free:
- Yes
- Warranty:
- 18 months
- Electrical Shock Protection Class:
- class II IEC 61140
- Sale Per Indivisible Quantity:
- 1
- Environmental Disclosure:
- ENVPEP1710010EN
- Ambient Air Temperature For Storage:
- -40-70 °C
- Sustainable Offer Status:
- Green Premium product
- Product Or Component Type:
- complete emergency stop push-button
- Contacts Type And Composition:
- 1 NO + 2 NC
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Type Of Keylock:
- key 200
- Operating Travel:
- 1 mm NC changing electrical state) || 2 mm NO changing electrical state) || 3.5 mm total travel)
- Reset:
- turn to release
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Electrical Reliability:
- λ < 10exp(-8) 5 V, 1 mA with confidence level of 90 % IEC 60947-5-4
- Operating Position:
- any position
- Range Of Product:
- Harmony XB6
- Ip Degree Of Protection:
- IP65 IEC 60529
- Width:
- 30 mm
- Depth:
- 77 mm
- Mounting Diameter:
- 16 mm
- Operator Profile:
- red mushroom à 30 mm, unmarked
- Device Short Name:
- XB6
- Shape Of Signaling Unit Head:
- round
- Standards:
- UL 508 || JIS C 852 || CSA C22.2 No 14 || IEC 60947-5-1 || IEC 60204-1 || ISO 13850 || IEC 60947-5-5 || JIS C8201-5-1 || IEC 60947-1 || JIS C8201-1
- Rohs Exemption Information:
- Yes
- Terminals Description Iso N°1:
- (31-32)NC || (13-14)NO || (21-22)NC
- Vibration Resistance:
- +/- 3 mm 2-500 Hz)IEC 60068-2-6 || 5 gn 2-500 Hz)IEC 60068-2-6
- Type Of Operator:
- trigger action and mechanical latching
- Short-Circuit Protection:
- 6 A cartridge fuse gG
- Ambient Air Temperature For Operation:
- -25-70 °C
- Contacts Material:
- silver alloy (Ag/Ni)
- Contacts Usage:
- standard
- Contact Operation:
- slow-break
- China Rohs Regulation:
- X
- Mercury Free:
- Yes
- Circularity Profile:
- ENVEOLI1710010EN
- Net Weight:
- 0.041 kg
- Product Certifications:
- CSA || CCC || GOST || UL
- [Ui] Rated Insulation Voltage:
- 250 V 3)IEC 60947-1
- Connections - Terminals:
- Faston connectors 2.8 x 0.5 mm
- Height:
- 30 mm
- Operating Force:
- 3.5 N NO changing electrical state || 4.5 N NC changing electrical state
- [Ie] Rated Operational Current:
- 3 A 120 V, AC-15, B300 IEC 60947-5-1 || 1.5 A 240 V, AC-15, B300 IEC 60947-5-1 || 0.1 A 250 V, DC-13, R300 IEC 60947-5-1 || 0.22 A 125 V, DC-13, R300 IEC 60947-5-1
- Protective Treatment:
- TC
- Datasheet:
- View