- Local Signalling:
- LED green power power ON || LED red error error || LED yellow state 1 safety output instantaneous || LED yellow state 2 safety output delayed || LED yellow start 1 start || LED yellow start 2 start || LED yellow S12 safety input S12 || LED yellow S22
- Type Of Start:
- automatic/manual/monitored
- Product Certifications:
- TÃV || cULus
- [Us] Rated Supply Voltage:
- 24 V AC - 15...10 % || 24 V DC - 20...20 %
- Input Compatibility:
- normally closed circuit ISO 14119 || mechanical contact ISO 14119 || OSSD pair IEC 61496-1-2 || normally closed circuit ISO 13850 || 3-wire proximity sensors PNP
- Ambient Air Temperature For Operation:
- -25-55 °C
- [Ith] Conventional Free Air Thermal Current:
- 0
- Connections - Terminals:
- removable screw terminal block, 0.2...2.5 mm² solid or flexible || removable screw terminal block, 0.25...2.5 mm² flexible with ferrule single conductor || removable screw terminal block, 0.2...1.5 mm² solid or flexible twin conductor || removable
- Mounting Support:
- 35 mm symmetrical DIN rail
- Rohs Exemption Information:
- Yes
- Maximum Response Time On Input Open:
- 20 ms
- Auxiliary Contact Composition:
- 2 NO immediate || 1 NO configurable
- [Ie] Rated Operational Current:
- 5 A AC-1 for normally open relay contact || 3 A AC-15 for normally open relay contact || 5 A DC-1 for normally open relay contact || 3 A DC-13 for normally open relay contact
- Ambient Air Temperature For Storage:
- -25-85 °C
- Relative Humidity:
- 5-95 % non-condensing
- Minimum Output Voltage:
- 24 V relay output
- Net Weight:
- 0.350 kg
- Height:
- 100 mm
- Sustainable Offer Status:
- Green Premium product
- Electrical Circuit Type:
- NC pair || OSSD pair
- Product Or Component Type:
- safety module
- [Ui] Rated Insulation Voltage:
- 250 V 2)IEC 60947-1
- Power Consumption In Va:
- 5 VA 24 V AC 50/60 Hz
- [Uimp] Rated Impulse Withstand Voltage:
- 4 kV II IEC 60947-1
- Safety Reliability Data:
- MTTFd > 30 years ISO 13849-1 || Dcavg >= 99 % ISO 13849-1 || PFHd = 0.98E-09 for SS0 ISO 13849-1 || PFHd = 0.96E-09 for SS1 ISO 13849-1 || HFT = 1 IEC 62061 || PFHd = 0.98E-09 for SS0 IEC 62061 || PFHd = 0.96E-09 for SS1 IEC 62061 || SFF > 99% IEC 62
- China Rohs Regulation:
- X
- Width:
- 22.5 mm
- Safety Level:
- can reach PL e/category 4 for normally open relay contact ISO 13849-1 || can reach SILCL 3 for normally open relay contact IEC 62061 || can reach SIL 3 for normally open relay contact IEC 61508 || can reach PL c/category 1 for normally closed relay c
- Minimum Output Current:
- 20 mA relay output
- Environmental Disclosure:
- ENVPEP1811003EN
- Maximum Line Resistance:
- 500 Ohm
- Depth:
- 120 mm
- Power Consumption In W:
- 2 W 24 V DC
- Safety Module Application:
- for emergency stop and protective guard applications || for OSSD monitoring
- Standards:
- IEC 60947-5-1 || IEC 61508-1 functional safety standard || IEC 61508-2 functional safety standard || IEC 61508-3 functional safety standard || IEC 61508-4 functional safety standard || IEC 61508-5 functional safety standard || IEC 61508-6 functional
- Range Of Product:
- Harmony Safety Automation
- Ip Degree Of Protection:
- IP20 terminals)IEC 60529 || IP40 housing)IEC 60529 || IP54 mounting area)IEC 60529
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Synchronisation Time Between Inputs:
- 0.5 s || 2 s
- Number Of Outputs:
- 3 on/off configurable pulsed output
- Function Of Module:
- emergency stop button with 2 NC contacts || guard monitoring with 1 or 2 limit switches || light curtain monitoring || RFID switch || monitoring of electro-sensitive protection equipment (ESPE)
- Input Protection Type:
- internal, electronic
- Associated Fuse Rating:
- 6 A gG NO relay output circuit IEC 60947-1
- Mercury Free:
- Yes
- Input/Output Type:
- semiconductor output 24 V DC, 20 mA Z1, not safety-related
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Time Delay Range:
- 0...900 s off
- Circularity Profile:
- ENVEOLI1811003EN
- Number Of Inputs:
- 2 positive safety input 24 V DC 5
- Safety Module Name:
- XPSBAT
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)