- [Ui] Rated Insulation Voltage:
- 300 V 2)IEC 60647-5-1, DIN VDE 0110 part 1
- Minimum Output Voltage:
- 17 V relay output
- Safety Use Category:
- category 4 maximum EN 954-1/EN/ISO 13849-1 || PLE maximum ISO 13849-1 || SIL 3 maximum IEC 61508
- Output Thermal Current:
- 4 A for both outputs simultaneously || 6 A for 1 output and 2 A for the other relay output
- Supported Modbus Function:
- 01 8-bit output data/32-bit input data || 02 32-bit input data/8-bit output data || 03 information and errors
- Method Of Access:
- slave
- Rohs Exemption Information:
- Yes
- Output Type:
- 2 relays, 2 NO contacts (4 NO total) || solid state, 6, volt-free
- Function Of Module:
- dynamic monitoring of hydraulic valves on linear presses || eccentric press || emergency stop monitoring, with or without time delay, 1 or 2-channel wiring || enabling switch monitoring, 2 or 3 contacts || foot switch monitoring || guard monitoring f
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Width:
- 74 mm
- [Uc] Control Circuit Voltage:
- 28.8 V
- Exchange Size:
- 14 words
- Synchronisation Time Between Inputs:
- depending on configuration selected
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Circularity Profile:
- ENVEOLI1406025EN
- Response Time:
- configurable : 20 ms or 30 ms with software XPSMCWIN
- Ambient Air Temperature For Operation:
- -10-55 °C
- [Uimp] Rated Impulse Withstand Voltage:
- 4 kV III IEC 60647-5-1, DIN VDE 0110 part 1
- Safety Module Name:
- XPSMC
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Number Of Inputs:
- 32
- Warranty:
- 18 months
- Power Consumption In W:
- 12 W
- Depth:
- 153 mm
- Product Or Component Type:
- configurable safety controller
- Safety Level:
- can reach PL e/category 4 EN 954-1/EN/ISO 13849-1 || can reach SIL 3 IEC 61508
- China Rohs Regulation:
- X
- Maximum Line Resistance:
- 100 Ohm <2000 m
- Environmental Disclosure:
- ENVPEP1406025EN
- Sustainable Offer Status:
- Green Premium product
- Mounting Support:
- mounting plate
- Data Format:
- 1 start bit/8 data bits || 1 stop bit even or odd || 2 stop bits without parity || RTU (Remote Terminal Unit) mode
- [Ith] Conventional Free Air Thermal Current:
- 16 A relay output || 6.5 A static output circuit
- Communication Port Protocol:
- Modbus 1 RJ45, serial link 1200 bps, 2400 bps, 4800 bps, 9600 bps or 19200 bps || Profibus 1 SUB-D 9-pin female, serial link 12 Mbps
- Breaking Capacity:
- 2 A 24 V static output circuit || 1.5 A 24 V DC-13)50 ms relay output
- Input Protection Type:
- external fuse 16 A
- Pvc Free:
- Yes
- Minimum Output Current:
- 10 mA relay output
- Height:
- 151.5 mm
- Associated Fuse Rating:
- 16 A gL power supply || 4 A gL relay output || 6 A fast blow relay output
- Local Signalling:
- 48 LEDs
- [Us] Rated Supply Voltage:
- 24 V DC - 20...20 %
- Standards:
- EN 954-1/EN/ISO 13849-1 || IEC 61496-1 || IEC 61508 || IEC 60204-1 || EN 1760-1/ISO 13856-1 || EN 574/ISO 13851 || IEC 60947-5-1
- Mercury Free:
- Yes
- Ambient Air Temperature For Storage:
- -25-85 °C
- Ip Degree Of Protection:
- IP20 conforming to IEC 60529
- Number Of Addresses:
- 1-125 Profibus || 1-247 Modbus
- Net Weight:
- 0.84 kg
- Breaking Capacity:
- 180 VA holding AC-15 C300 relay output || 1800 VA inrush AC-15 C300 relay output
- Range Of Product:
- Preventa Safety automation
- Parity:
- even Modbus || no Modbus || odd Modbus
- Type Of Start:
- configurable
- Product Certifications:
- CSA || UL || TÃV
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- QN-QUOTE-REQUEST: