null

Automation Distribution helps you design, build, and support high-performance automation cells with SMC, Universal Robots, WAGO, Turck, PULS, Zebra, Yaskawa and more.

SMC HRSC040-A-20-T1-X191 Thermo-Chiller - 4.1 kW CO2, High-Pressure Pump, Custom Configuration | Industrial

SMC
SKU:
HRSC040-A-20-T1-X191
Availability:
Factory stock
$19,457.48
Condition:
New
Current Stock:
The SMC HRSC040-A-20-T1-X191 is a medium capacity air-cooled thermo-chiller with high-pressure pump and custom configuration delivering 4.1 kW cooling using CO2 refrigerant (GWP 1). PID-controlled ±0.1°C temperature stability, 5-40°C range. Air-cooled ?68 dB(A). NPT thread with Rc-NPT fitting. Single-phase 200-230 VAC (50/60Hz). High-pressure pump with custom X191 configuration for specialized applications. Heating function, RS-232C/RS-485 communication, auto-restart, anti-freeze protection, alarm monitoring. Compatible with tap water, deionized water, or 15% glycol solution. Compact 377mm width. EPA, CARB, EU compliant. UL/CE certified.
Series:
HRSC
Cooling Capacity (60Hz):
4200 W (4.2 kW)
Heating Capacity (60Hz):
1100 W
Refrigerant:
R744 (CO2)
GWP:
1
Cooling Method:
Air-cooled refrigeration
Temperature Control:
PID
Temperature Stability:
±0.1°C
Set Temperature Range:
5 to 40°C
Power Supply:
1-phase 200-230 VAC (50/60Hz)
Rated Current (50/60Hz):
11.4/11.5 A
Power Consumption (50/60Hz):
1.8/1.8 kW
Earth Leakage Breaker:
20 A / 30 mA
Pump Type:
High Pressure
Pump Output:
550 W
Rated Flow (50/60Hz):
27/29 L/min
Max Flow (50/60Hz):
34/40 L/min
Tank Capacity:
Approx. 5 L
Circulating Fluid:
Water, 15% ethylene glycol aqueous solution
Circulating Fluid Port:
Rc1/2
Pipe Thread Conversion:
NPT (with Rc-NPT fitting)
Noise Level (50/60Hz):
64/66 dB(A)
Ambient Temperature:
5 to 40°C
Ambient Humidity:
30 to 70% (no condensation)
Max Altitude:
3000 m
Installation:
Indoor only
Refrigerant Charge:
0.48 kg
Weight (dry):
Approx. 73 kg
Communication:
RS-232C, RS-485
Remote Control:
No
Contact I/O:
No
Custom Configuration:
X191
Heating Function:
Yes
Auto Restart:
Yes
Anti-Freeze Protection:
Yes
Self-Diagnosis:
Yes
Compliance:
EPA, CARB, EU F-gas
Certifications:
UL, CE
Fluid Contact Materials:
Stainless steel, Copper (brazing), Brass, Alumina ceramic, Carbon, PP, PE, POM, FKM, EPDM, PVC, SiC