Communication interface, can be used with WAGO USB Communication Cable (750-923) or IO-Link Communication Module (2789-9080) or Modbus RTU Communication Module (2789-9015)
conformity marking:
CE
connection technology:
CAGE CLAMP«
connection technology 2:
Push-in CAGE CLAMP«
connection type 1:
Input/signaling
connection type 2:
Output
control deviation:
«± 1 %
country of origin sales organisation germany:
CN
current limitation:
1.1 x Io nom (typ.)
default setting:
DC 24 V
depth from upper edge of din rail:
130 mm / 5.118 inch
derating:
See instruction leaflet
efficiency typ:
96.1 % (400 VAC: 40 A: 25 C)
fine stranded conductor:
0.08 ª 2.5 mm / 28 ª 12 AWG
fine stranded conductor 2:
0.5 ª 10 mm / 20 ª 8 AWG
fine stranded conductor with insulated ferrule:
0.25 ª 1.5 mm / 20 ª 16 AWG
fine stranded conductor with insulated ferrule 2:
0.5 ª 6 mm
fine stranded conductor with uninsulated ferrule:
0.25 ª 2.5 mm / 20 ª 14 AWG
fine stranded conductor with uninsulated ferrule 2:
0.5 ª 6 mm
fire load:
0.000 MJ
height:
130 mm / 5.118 inch
input current ii:
«± 3 x 1.7 A (400 VAC: 40 ADC)
input voltage range:
(2 / 3) x AC 340 ª 550 V
inrush current:
«± 15 A (after 1 ms)
internal fuse:
3 x T 3.2 A / 500 VAC
isolation voltage pri sec ac:
3510 V
isolation voltage sec gnd:
DC 0.5 kV
isolation voltage sec signal:
DC 0.5 kV
mains failure hold up time:
« 20 ms (3 x 400 VAC)
mounting type:
DIN-35 rail
mtbf:
> 800,000 h (per IEC 61709)
nominal input voltage ui nom:
(2 / 3) x AC 400 ª 500 V
nominal mains frequency range:
47 ª 63 Hz: 0 Hz
nominal output current io nom:
40 A (24 VDC)
nominal output power:
960 W
nominal output voltage uo nom:
DC 24 V (SELV)
note dimensions:
Height without connector || Height with connector: 169 mm
open circuit proof:
Yes
operating altitude max:
5000 m
output voltage range:
DC 24 ª 28 V (adjustable)
overload behavior:
TopBoost/PowerBoost/Time-limited constant current mode (other overload behaviors can be set)
overvoltage category:
III («± 2000 m a. s.l.): II (> 2000 m a. s.l.)
overvoltage protection secondary:
Internal protective circuit || «± 35 VDC (in the event of a fault)
packaging type:
Box
parallel operation:
Yes
phases:
2 || 3
pollution degree:
2
power factor correction pfc:
Active
powerboost:
DC 60 A (5 s)
protection class:
I
protection type:
IP20 (per EN 60529)
recommended backup fusing:
3 x 16 A (for USA/Canada: 3 x 15 A)
relative humidity:
5 ª 96 % (no condensation permissible)
required backup fusing:
An external DC fuse is required for the DC input voltage.
residual ripple:
«± 70 mV (Peak-to-peak)
resistance to reverse feed:
«± DC 35 V
series operation:
Yes
short circuit protected:
Yes
signaling:
Optical status indication (DC OK: load: warning and error states) || Digital signal input and output (DI/DO)
solid conductor:
0.08 ª 2.5 mm / 28 ª 12 AWG
solid conductor 2:
0.5 ª 10 mm / 20 ª 8 AWG
standards specifications:
EN 61010-1 || EN 61010-2-201 || EN 61204-3 || UL 61010-1 || UL 61010-2-201
strip length:
8 ª 9 mm / 0.31 ª 0.35 inch
strip length 2:
13 ª 15 mm / 0.51 ª 0.59 inch
surrounding air temperature operation:
-25 ª 70 C (Device starts at ª40 C (type-tested))